CyberPower Systems CS24C12V-E Communication Signals, Specification, Limited Warranty, Fcc Notice

Models: CS24C12V-E

1 2
Download 2 pages 33.04 Kb
Page 2
Image 2
COMMUNICATION SIGNALS

SPECIFICATIONBack Panel

ModelCS24C12V2-EInputOutputBatteryWarning DiagnosticsManagement / CS24C12V2-E

INPUT: 100-240V~ 50-60Hz ; 0.75A OUTPUT: 12V 24W

CAUTION:

RISK OF ELECTRICAL SHOCK. DO NOT REMOVE COVER.

NO USER SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED

SERVICE PERSONNEL. FOR USE IN A CONTROLLED ENVIRONMENT.

REFER TO MANUAL FOR ENVIRONMENTAL CONDITIONS.

FCC CLASS B VERIFIED

 

US

 

LISTED

 

68FG

 

E235457

Contains sealed nonspillable lead acid battery.

Made In China

Must be properly recycled or disposed.

CS24C12V2-E

COMMUNICATION SIGNALS

The communication signals of this unit are isolated from the internal circuitry via open collector opto- coupled transistors. The connection “SIG RTN” (Signal Return) is a common return point for all communication signals. In the typical application, the attached equipment digital ground connects to Signal Return, and pull-up resistors turn the open collector signals into logic levels.

 

CS24C12V2-E

 

 

CS24C12V2-E

Message

 

 

12V

+ Voltage output

 

 

12V RTN

- Voltage output

SIG RTN

Signal return

ON BATTERY

Low when operating from utility line.

 

Open when operating from battery.

REPLACE

Low when battery is charged.

BATTERY

Open when battery fails the Self Test.

BATTERY

Low when battery is present.

MISSING

Open when battery is missing.

LOW BATTERY

Low when battery is near full charge capacity.

 

Open when operating from a battery with < 20%

 

capacity.

 

 

SPECIFICATION

Model

CS24C12V2-E

Input

 

 

 

Voltage Range

85Vac - 264Vac (Universal Input)

Frequency Range

47 - 70 Hz

 

 

Output

 

On Battery Output Voltage

12Vdc

Continuous Power Capability

24W

 

 

Output Power Max

24W

Efficiency (at 75% Max Load)

> 75 %

 

 

Battery

 

Battery Type

Sealed, Maintenance Free Lead-Acid Battery

Numbers of Battery

7.2AH / 12V x 1

Typical Recharge Time

18Hours

 

 

Replaceable

Yes

Surge Protection and Filtering

 

 

 

Lightning / Surge Protection

Yes

Warning Diagnostics

 

Indicators

AC, Output, Battery

 

 

Management

 

Auto-Charge

Yes

 

 

Communication Interface

On Battery, Replace Battery, Battery Missing,

 

Low Battery

 

 

Physical

 

 

 

Maximum Dimensions (L*W*D)

27.5cm x 20.4cm x 9.9cm

Weight (kg)

3.51

 

 

Environment

 

Operating Temperature

5oF - 122oF (-15oC - 50oC)

Operating Humidity

0 - 95% noncondensing within enclosure

Max Operating Elevation

10,000ft (3,000m)

Max Storage Elevation

50,000ft (15,000m)

 

 

Storage Temperature

5oF - 122oF (-15oC - 50oC)

LIMITED WARRANTY

CyberPower warrants to you, the Initial Purchaser, that the Product will be free from defects in material and workmanship for three years from the date of original purchase, subject to the terms of this Limited Warranty. This Limited Warranty gives you specific rights, and you may have other rights, which vary from State to State or Province to Province.

Any Implied Warranty of Merchantability or for Fitness for a Particular Purpose, if applicable to the Product, is limited in duration to three years. This provision shall NOT create any Implied Warranty or Merchantability or of Fitness for a Particular Purpose that would not otherwise apply to the Product. NOTE: Some States and Provinces do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.

To be covered you must still be the owner of the Product at the time of the failure that results in the claim made under this Limited Warranty. Your sole and exclusive remedies are those provided by this Limited Warranty. This exclusion of other express warranties applies to written and oral express warranties. CyberPower excludes any liability for personal injury. CyberPower excludes any liability for direct, indirect, special, incidental, or consequential damages, whether for damage to or loss of property, loss of profits, business interruption, information or data. This exclusion applies even though damage or loss is caused by negligence or other fault. NOTE: Some States or Provinces do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation may not apply to you.

DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT OR OTHER HIGH RISK ACTIVITIES.

CyberPower does not sell the PRODUCT for use in high-risk activities. The PRODUCT is not designed or intended for use in hazardous environments requiring fail-safe performance, including the operation of nuclear facilities, aircraft navigation or communication systems, air traffic control, weapons systems, life support or medical applications or for use in any circumstance in which the failure of the PRODUCT could lead directly to death, personal injury, or severe physical or property damage, or that would affect operation or safety of any medical or life support device (collectively, "High Risk Activities").

CyberPower expressly disclaims any express or implied warranty of fitness for High Risk Activities. CyberPower does not authorize use of any PRODUCT in any High Risk activities.

ANY SUCH USE IS IMPROPER AND IS A MISUSE OF A CYBERPOWER PRODUCT.

The Limited Warranty is governed by the laws of the United States and the State of Minnesota, without reference to conflict of law principles. The application of the United Nations Convention of Contracts for the International Sale of Goods is expressly excluded

FCC NOTICE:

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with these instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: (1)Reorient or relocate the receiving antenna.

(2)Increase the separation between the equipment and receiver. (3) Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. (4) Consult the dealer or an experienced radio/TV technician for help.

CAUTION: Shielded signal cables must be used with this device to ensure compliance with Class B FCC limits.

CAUTION: Any changes or modifications not expressly approved by Cyber Power could void the authority granted by the FCC to operate this equipment.

For more information, please contact:

 

 

CyberPower Systems ( USA ), Inc. 4241 12th Avenue East, Suite 400, Shakopee, MN55379

Phone: (952)403-9500 Fax: (952)403-0009

www.cpsww.com

CyberPower Systems ( EUROPE ), Inc. Flight Forum 3545, 5657DW Eindhoven, The Netherlands

E-mail: sales@cyberpower-eu.com

eu.cyberpowersystems.com

K01-2412H10-00

Page 2
Image 2
CyberPower Systems CS24C12V-E Communication Signals, Specification, Limited Warranty, Fcc Notice, Model, CS24C12V2-E