| 5. Replace the new battery pack. Assemble |
4. Remove the retaining screw of | the screws, cover, cable and front panel in |
the reverse sequence of above steps. | |
the cable connectors. | Recharge the unit for |
| the UPS performs expected runtime |
DEFINITIONS FOR ILLUMINATED LCD INDICATORS
Line mode
Select SW | UPS Status Display |
| Capacity | Digital Value Display |
|
| |||||||
Press |
|
|
|
|
| Display |
|
|
|
|
|
| |
|
|
|
|
|
| Load |
| Battery | Input | Output | Run | % of | % of |
|
|
|
|
|
| Cap. |
| Cap. | Voltage | Voltage | Time | Load | Batt. |
Initial | V | X |
| X | V |
| X |
| V |
|
|
| |
1st | V | X |
| X | V |
| X |
|
| V |
|
| |
2nd | V | X |
| X | V |
| X |
|
|
| V |
| |
3rd | V | X |
| X | X |
| V |
|
|
|
| V | |
4th | V | X |
| X | V |
| X | V |
|
|
|
| |
5th(Return) | V | X |
| X | V |
| X |
| V |
|
|
| |
Press >3sec | V | X | V |
| X |
| |||||||
(Sound |
|
|
|
|
|
|
|
|
|
|
|
|
|
Disable) |
|
|
|
|
|
|
|
|
|
|
|
|
|
Press >3sec | V | X | X |
| X |
| |||||||
again(Sound |
|
|
|
|
|
|
|
|
|
|
|
|
|
Enable) |
|
|
|
|
|
|
|
|
|
|
|
|
|
(Overload) | V | X |
| V |
|
"V" : Illuminated, "X" : Not Illuminated,
Battery mode
Select SW | UPS Status Display |
| Capacity | Digital Value Display |
|
| |||||||
Press |
|
|
|
|
| Display |
|
|
|
|
|
| |
|
|
|
|
|
| Load |
| Battery | Input | Output | Run | % of | % of |
|
|
|
|
|
| Cap. |
| Cap. | Voltage | Voltage | Time | Load | Batt. |
Initial | X | V |
| X | V |
| X |
| V |
|
|
| |
1st | X | V |
| X | V |
| X |
|
| V |
|
| |
2nd | X | V |
| X | V |
| X |
|
|
| V |
| |
3rd | X | V |
| X | X |
| V |
|
|
|
| V | |
4th | X | V |
| X | V |
| X | V |
|
|
|
| |
5th(Return) | X | V |
| X | V |
| X |
| V |
|
|
| |
Press >3sec | X | V | V |
| X |
| |||||||
(Sound |
|
|
|
|
|
|
|
|
|
|
|
|
|
Disable) |
|
|
|
|
|
|
|
|
|
|
|
|
|
Press >3sec | X | V | X |
| X |
| |||||||
again(Sound |
|
|
|
|
|
|
|
|
|
|
|
|
|
Enable) |
|
|
|
|
|
|
|
|
|
|
|
|
|
(Overload) | X | V |
| V |
|
"V" : Illuminated, "X" : Not Illuminated,
TROUBLE SHOOTING
Problem | Possible Cause | Solution | |
| Turn the UPS off and unplug at least one | ||
protection outlets |
| ||
Circuit breaker has tripped | piece of equipment. Wait 10 seconds, | ||
stop providing | |||
due to an overload. | reset the circuit breaker by depressing the | ||
power to | |||
| button, and then turn the UPS on. | ||
equipment. |
| ||
|
| ||
The UPS does | Battery not fully charged. | Recharge the battery by leaving the UPS | |
plugged in. | |||
not provide |
| ||
expected |
|
| |
runtime. | Battery is slightly worn out. | Contact CyberPower Systems about | |
|
| replacement batteries at | |
|
| ||
| The on/off switch is | Turn the UPS off. Wait 10 seconds and | |
| designed to prevent | ||
| damage by rapidly turning it | then turn the UPS on. | |
| off and on. |
| |
The UPS will not | The battery is worn out. | Contact CyberPower Systems about | |
turn on. | replacement batteries at | ||
|
| ||
| Mechanical problem. | Contact CyberPower Systems at | |
| |||
|
| ||
|
|
| |
| The USB cable is not | Connect the USB cable to the UPS unit | |
PowerPanel® | and an open USB port on the back of the | ||
connected. | |||
Business Edition |
| computer. | |
The unit is not providing | Shutdown your computer and turn the | ||
is inactive. | |||
UPS off. Wait 10 seconds and turn the | |||
battery power. | |||
| UPS on. This should reset the unit. | ||
|
|
Additional troubleshooting information can be found at eu.cyberpowersystems.com
TECHNICAL SPECIFICATIONS
Model | OR1000ELCDRM1U |
| OR1500ELCDRM1U | |
Capacity (VA) | 1000VA/600W |
| 1500VA/900W | |
Input |
|
|
| |
Input Voltage Range | 160VAC~270VAC | |||
Frequency Range | 50/60Hz (Auto Sensing) | |||
AVR Function | Boost Only | |||
Output |
|
|
| |
On Battery Output | 230Vac | |||
Voltage | ||||
|
|
| ||
On Battery Output | 50/60Hz | |||
Frequency | ||||
|
|
| ||
Transfer Time | 4ms Typical | |||
Overload Protection | On Utility: Circuit Breaker, On Battery: Internal Current Limiting | |||
Surge Protection |
|
|
| |
Lightning / Surge |
| Yes | ||
Protection |
| |||
|
|
| ||
Network/ Phone/ Fax/ | RJ11/RJ45 ( One In/ One Out ) | |||
Modem Protection | ||||
|
|
| ||
Operating Temperature | +32°F to 104°F ( 0°C to 40°C ) | |||
Physical |
|
|
| |
Total # of UPS outlets | IEC320 C 13 x 6 ( Backup x 4 ) | |||
Maximum | 1U Rack 43.3 x 38.9 x 4.4 |
| 1U Rack 43.3 x 48.5 x 4.4 | |
Dimensions(cm) |
| |||
|
|
| ||
Weight (kg) | 16.1 |
| 19.4 | |
Battery |
|
|
| |
Sealed Maintenance | 6V / 7Ah x4 |
| 6V / 9Ah x4 | |
Free Lead Acid Battery |
| |||
|
|
| ||
Typical Recharge Time |
| 8 hours | ||
Charging Current(Max.) |
| 1A | ||
User Replaceable |
| Yes | ||
Status Indicators |
|
|
| |
Indicators | Power On, Wiring Fault, LCD Display | |||
Audible Alarms | On Battery, Low Battery, Overload | |||
Communication |
|
|
| |
PowerPanel® Business | Windows 2000/NT/XP/Vista,Mac OSX,Linux | |||
Edition Software | ||||
|
|
| ||
Management |
|
|
| |
Self |
| Yes | ||
| Yes | |||
| Yes | |||
USB interface |
| Yes | ||
Dry contact Closure |
| Yes | ||
SNMP/HTTP |
| Optional | ||
Networking |
| |||
|
|
|
CYBERPOWER GREENPOWER UPS TECHNOLOGY
Our new UPS circuit is designed to save energy operating in GreenPower
Bypass Mode.
A traditional UPS circuit with AVR provides normal output voltage through the Relay and AVR transformer. The current travels first through the transformer conducting energy and generating heat. This heat creates energy dissipation resulting in a "Power Loss" or consumption of utility power and money.
CyberPower's GreenPower Circuit Design is a solution to this "Power Loss." When the Utility Power is operating normally, our Green Power UPS works in Bypass Mode. Our GreenPower design conducts power only through the Relay and still provides normal output voltage. Bypassing the transformer reduces power consumption thereby conserving energy and saving money. When the utility power is abnormal the UPS will operate under Battery or AVR Mode. Under this condition Green Power UPS and a traditional UPS would operate about the same.
On average utility power operates 88% of the time and the CyberPower GreenPower Technology will work in its money/energy saving Bypass Mode.
For more information, visit eu.cyberpowersystems.com or contact
CyberPower Systems B.V.
Flight Forum 3545 5657DW Eindhoven The Netherlands
Tel: +31 40 2348170,
CyberPower Systems Inc. (USA) 4241 12th Avenue East, Suite 400, Shakopee, MN 55379, U.S.A. Tel: +1 952 4039500, Fax: +1 952 4030009,
Entire contents copyright ©2004 CyberPower Systems B.V., All rights reserved. Reproduction in whole or in part without permission is prohibited. PowerPanel® and PowerPanel® Plus are trademarks of CyberPower Systems (USA) Inc.