CyberPower Systems UP500E Battery Replacement Procedure, Storage, Technical Specifications, Model

Models: UP750E UP500TE UP500E UP350TE

1 2
Download 2 pages 30.51 Kb
Page 2
Image 2
BATTERY REPLACEMENT PROCEDURE:

BATTERY REPLACEMENT PROCEDURE:

For UP500E/UP750E only

1.Remove the 2 retaining screws then push the battery cover backward and remove the cover.

2.Lean the UPS to one side and pull out the battery partially from the compartment.

Disconnect the battery wires from the battery, and then remove the battery from the compartment.

3. Install the replacement battery by connecting the red wire to the positive (+) terminal of the battery and connecting the black wire to the negative (-) terminal of the battery.

4.Slide the battery back into the compartment. Turn the UPS upside

down to help the batteries entirely slide into the compartment. Replace the cover and the retaining screws.

REMINDER: Recharge the unit for 4 – 8 hours to ensure the UPS performs expected runtime

STORAGE

First turn off your UPS and disconnect its power cord from the wall outlet. Disconnect all cables connected the UPS to avoid battery drain. To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months to insure battery life. If the battery remains uncharged for an extended period of time, it may suffer permanent loss of capacity.

TECHNICAL SPECIFICATIONS

Model

 

UP350TE

 

UP500TE

 

UP500E

 

UP750E

Capacity

(VA)

350VA

 

500VA

 

500VA

 

750VA

Capacity

(Watts)

210W

 

300W

 

325W

 

450W

Input

 

 

 

 

 

 

 

 

Input Voltage Range

 

 

220-240Vac

 

Frequency Range

 

 

 

50/60 Hz

 

Output

 

 

 

 

 

 

 

 

On Battery Output

 

 

Simulated Sine Wave at 230Vac +/- 7%

 

Voltage

 

 

 

 

 

 

 

 

 

 

 

 

On Battery Output

 

 

 

50/60 Hz

 

Frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

Overload Protection

On Utility: Fuse, On Battery: Internal Current Limiting

Surge Protection and Filtering

 

 

 

 

 

 

Lightning / Surge

 

 

 

 

Yes

 

Protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Network Protection

 

 

RJ45 (One In/One Out)

 

Physical

 

 

 

 

 

 

 

 

Total # of UPS

 

2

 

2

 

Receptacles

 

 

 

 

 

 

 

 

 

 

Maximum Dimensions

23.8cm*8.0cm*13.7cm

 

28.3cm*9.1cm*16.4cm

Weight (Kg)

4.4

 

5.0

 

6.4

 

7.5

Battery

 

 

 

 

 

 

 

 

Sealed Maintenance

 

 

 

 

 

 

 

Free Lead Acid

12V / 4AHx1

 

12V / 4.5AHx1

 

12V / 7AH x1

 

12V / 9AH x1

Battery

 

 

 

 

 

 

 

 

User Replaceable

 

N/A

 

Yes, Hot Swappable Battery Pack

Typical Recharge

 

 

 

8 Hours

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

Warning Diagnostics

 

 

 

 

 

 

 

Indicators

 

 

 

Power On, Using Battery, Boost, Buck

 

Audible Alarms

 

 

On Battery, Low Battery, Overload

 

Environmental

 

 

 

 

 

 

 

Operating

 

 

 

+32°F to 95°F ( 0°C to 35°C )

 

Temperature

 

 

 

 

 

 

 

 

 

 

Operating Relative

 

 

0 to 95% NON-CONDENSING

 

Humidity

 

 

 

 

 

 

 

 

 

 

 

 

Communication

 

 

 

 

 

 

 

PowerPanel®

 

 

Windows 98/ME/2000/NT/XP, Server 2003

 

Software

 

 

 

 

 

 

 

 

 

 

 

 

Management

 

 

 

 

 

 

 

Auto-Charger

 

 

 

 

Yes

 

Auto-Restart

 

 

 

 

Yes

 

DEFINITIONS FOR ILLUMINATED LED INDICATORS

TROUBLE SHOOTING

Problem

Possible Cause

Solution

The UPS does not

Batteries are not fully charged.

Recharge the battery by leaving the UPS

plugged in.

 

perform expected

 

 

 

Contact CyberPower Systems at

runtime.

Battery is slightly worn out.

 

sales@cyberpower-eu.com

 

 

 

 

 

 

The on/off switch is designed to

Turn the UPS off. Wait 10 seconds and then

 

prevent damage by rapidly

 

turn the UPS on.

 

turning it off and on.

 

 

 

 

 

The UPS will not

The unit is not connected to an

The unit must be connected to a 220-240V

AC outlet.

50/60Hz outlet.

turn on.

 

 

 

The battery is worn out.

Contact CyberPower Systems at

 

sales@cyberpower-eu.com

 

 

 

 

 

 

Mechanical problem.

Contact CyberPower Systems at

 

sales@cyberpower-eu.com

 

 

 

 

 

 

 

Turn the UPS off and unplug at least one piece

 

 

connected equipment. Unplug the power cord of

 

 

the UPS then remove the fuse compartment

 

 

beneath the power inlet of the UPS and replace

Power On

Using

Fuse

Alarm

 

Battery

On

Off

Normal

Off

 

 

 

 

Off

On

Normal

Two Beeps

 

 

 

 

Off

On

Normal

Rapid

Beeps

 

 

 

 

 

 

 

 

 

 

Two beeps

Off

On/Off

Blown

or rapid

 

 

 

beeps

 

 

 

 

Off

On/Off

Normal/

Long Beep

Blown

 

 

 

Condition

Normal

Utility Failure- The UPS is providing battery power to the Battery-Power Supplied outlets.

Utility Failure- The UPS is providing battery power. The rapid beeps indicate the battery will run out of charge within a few minutes. Overload- Occurs in the Full-time Surge Protection Outlets. Please turn the UPS off and unplug at least one piece of equipment from the UPS. Replace the fuse with a spare one then turn the UPS on.

Overload- Occurs in the Battery-power Supplied Outlets. Turn the UPS off and unplug at least one piece of equipment from the UPS. Check the fuse and do the replacement if necessary. Turn the UPS on.

 

Fuse is blown due to overload

the blown fuse with a spare one. Lock the

 

 

compartment back to the UPS. Connect power

Outlets do not

 

cord then turn the UPS on. Make sure that your

 

spare fuse meets the specification: 6.3A, 250V,

provide power to

 

 

5x10mm.

equipment

 

Batteries are discharged

Allow the unit to recharge for at least 4 hours.

 

 

 

 

 

Unit has been damaged by a

Contact CyberPower Systems at

 

surge or spike.

sales@cyberpower-eu.com

 

 

 

 

The serial cable is not

Connect the serial cable to the UPS unit and

 

an open serial port on the back of the

 

connected.

computer. You must use the cable that came

 

 

with the unit.

PowerPanel® is

The serial cable is connected to

Try another serial port of your computer.

the wrong port.

inactive (all icons

 

 

are gray).

The unit is not providing battery

Shutdown your computer and turn the UPS off.

 

Wait 10 seconds and turn the UPS back on.

 

power.

 

This should reset the unit.

 

 

 

The serial cable is not the cable

You must use the cable included with the unit

 

that was provided with the unit.

for the software.

For more information, visit eu.cyberpowersystems.com or contact CyberPower Systems B.V.

Flight Forum 3545, 5657DW Eindhoven, The Netherlands

TEL: +31 (0)40 2348170, FAX: +31 (0)40 2340314, E-MAIL: sales@cyberpower-eu.com

CyberPower Systems Inc. (USA)

4241 12th Avenue East Suite 400 Shakopee, MN 55379, U.S.A.

Tel: +1 952 4039500, Fax: +1 952 4030009, E-MAIL: sales@cyberpowersystems.com

Entire contents copyright ©2004 CyberPower Systems B.V., All rights reserved. Reproduction in whole or in part without permission is prohibited. PowerPanel® and PowerPanel® Plus are trademarks of CyberPower Systems (USA) Inc.