UMDAS 0802DA User's Guide | Functional Details |
In differential mode, the following two requirements must be met for linear operation:
!Any analog input must remain in the −10V to +20V range with respect to ground at all times.
!The maximum differential voltage on any given analog input pair must remain within the selected voltage range.
The input
−10 V to +20 V range in order to yield a useful result. For example, you input a 4 V pp sine wave to CHHI, and apply the same sine wave 180° out of phase to CHLO. The common mode voltage is 0 V. The differential input voltage swings from 4 V− (−4 V) = 8 V to (−4 V) − 4 V = −8V. Both inputs satisfy the
−10 V to +20 V input range requirement, and the differential voltage is suited for the ±10 V input range (see Figure
+4V
CHHI 0V
Measured Signal
8V Differential |
+4V
CHLO
Figure
If you increase the common mode voltage to 11 V, the differential remains at ±8 V. Although the [common- mode voltage + signal] on each input now has a range of +7 V to +15 V, both inputs still satisfy the −10 V to +20 V input requirement (see Figure
+15V
Measured Signal
CHHI +11V
8V Differential | |
|
CHLO +11V
+7V
Figure
If you decrease the
| Measured Signal | ||
| |||
CHHI | |||
| |||
| 3V |
| |
| |||
| 8V Differential |
Figure