Dayton 3VH19 manual Dayton Natural Gas Construction Heater, Troubleshooting Chart

Models: 3VH19

1 12
Download 12 pages 11.63 Kb
Page 8
Image 8
Troubleshooting Chart

Dayton Operating Instructions and Parts Manual

3VH19

Dayton® Natural Gas

Construction Heater

Troubleshooting Chart

 

 

 

Never attempt to service heater while it is connected to gas supply, operating, or hot. Severe burns can

 

 

 

 

 

 

 

 

occur.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Symptom

Possible Cause(s)

Corrective Action

 

 

Pilot fails to light

1. Natural gas supply valve closed on gas

1. Open natural gas supply valve slowly

 

 

 

 

 

supply

 

 

 

 

 

 

 

2. Allow several minutes to purge air with

 

 

 

 

 

2. Air in gas line

automatic control valve button depressed

 

 

 

 

 

3. Blockage in pilot orifice

3. Replace pilot orifice

 

 

 

 

 

4. Piezo ignition system not sparking

4. Adjust ignitor electrode gap to .120".

 

 

 

 

 

 

Check wire lead for damage. Replace

 

 

 

 

 

 

piezo ignitor and/or ignitor electrode as

 

 

 

 

 

 

necessary

 

 

 

 

 

 

 

Pilot lights but goes out when control

1. Not enough warm-up time

1. Relight, hold automatic control valve

 

 

valve knob is released

 

button in 45 seconds

 

 

 

 

 

2. Low gas pressure

2. Check natural gas for proper gas supply

 

 

 

 

 

3. Thermocouple loose or needs to be

3. Tighten connection or replace thermo-

 

 

 

 

 

replaced

couple

 

 

 

 

 

4. Control valve needs to be replaced

4. Replace control valve

 

 

 

 

 

 

 

Maximum Burn rate is low;

1. Main burner valve not fully open

1. Fully open main burner valve by turning

 

 

Emitter not glowing

 

the valve handle towards ON position

 

 

 

 

 

 

until it stops

 

 

 

 

 

2. Plugged gas orifices

 

 

 

 

 

 

 

2. Replace gas orifice

 

 

 

 

 

3. Low gas pressure

 

 

 

 

 

 

 

3. Consult natural gas supplier; check

 

 

 

 

 

 

regulator output

 

 

 

 

 

 

 

Soot forming inside heater,

1. Main burner valve not fully open

1. Adjust main burner valve slowly

 

 

flame 100% yellow

 

towards ON position

 

 

 

 

 

2. Low gas pressure

2. Consult natural gas supplier

 

 

 

 

 

 

 

 

Flames are extremely high. Coming out of louvers

1.Unit was connected to LP gas instead of natural gas

1.Check gas source, replace with natural gas supply

8