Delta Electronics DTE-2DS Setting up Communication, Selecting Channel, Setting up Copy Function

Models: DTE-2DS

1 2
Download 2 pages 59.75 Kb
Page 2
Image 2
For ON/OFF Control Application:

Parameter

 

 

 

and

 

 

 

 

 

 

can be set up when parameter

 

 

 

 

is set as “0”.

 

 

 

 

 

 

 

 

 

 

is not “0”.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

can be set up when

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

and

 

 

 

 

 

 

(control cycle for output 1) can be set up when parameter

 

is set as

 

 

 

 

(heating) or

 

 

 

(cooling) output.

 

 

 

(control cycle for output 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is set as

 

(heating) or

 

 

 

 

 

(cooling) output.

can be set up when parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

and

 

 

 

Can be set up when parameter

 

 

 

and

 

 

 

are set as

 

(heating) or

 

 

 

 

 

(cooling) output. (The settings in

 

and

 

 

 

have to be

 

 

 

 

 

 

 

 

 

 

different.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For ON/OFF Control Application:

1.Set up 2 outputs: Enter parameter For Manual Control Application: and For Programmable PID Application: in “initial setting mode” (see “Setting up

Parameters” section for details). Set up one of the two parameters as For Upper/Lower Limits of Control Output: or For Alarm Application: of control output.

2.Set up control type: Enter parameter Note: AL-H and AL-L include AL1H, AL2H and AL1L, AL2L. in “initial setting mode” (see “Setting up Parameters”

section for details) and set it up as Setting up Communication (ON/OFF) control.

3.Set up parameters: In “regulation mode”

Parameters Selecting Channel and Setting up Copy FunctionLocking the Keys on Panel (hysteresis for output 1) can be set up when parameter Analog Output & Temperature Tuning is set as Error Message (heating) How to Install (cooling) output. Manual background (hysteresis for output 2) can be

set up when parameter Manual background is set as Manual background (heating) or Manual background (cooling) output. You can

only set up Manual background when Manual background and Manual background are set as Manual background or Manual background at the same time.

Parameter Manual backgroundCan be set up when parameter Manual background and Manual background are set as control output,

and the settings in Manual background and Manual background are different, e.g. output 1 is Manual background (heating), and output

2 is Manual background (cooling).

For Manual Control Application:

1.Set up 2 outputs: Enter parameter Manual background and Manual background in “initial setting mode” (see “Setting up

Parameters” section for details). Set up one of the two parameters as Manual background or Manual background of control output.

2.Set up control type: Enter parameter Manual background in “initial setting mode” (see “Setting up Parameters”

section for details) and set it up as Manual background (manual) control.

3.Set up parameters: In “regulation mode”

Parameter Manual background and Manual backgroundManual background (control cycle for output 1) can be set up when parameter Manual background is set as Manual background (heating) or Manual background (cooling) output. Manual background (control cycle for output 2)

can be set up when parameter Manual background is set as Manual background (heating) or Manual background (cooling) output.

Parameter Manual background and Manual background (in “operation mode”)Manual background can be set up when parameter

Manual background is set as Manual background (heating) or Manual background (cooling) output. Manual background can be set up when

parameter Manual background is set as Manual background (heating) or Manual background (cooling) output.

For Programmable PID Application:

1.Set up 2 outputs: Enter parameter Manual background and Manual background in “initial setting mode” (see “Setting up

Parameters” section for details). Set up one of the two parameters as Manual background or Manual background of control output.

2.Set up control type: Enter parameter Manual background in “initial setting mode” (see “Setting up Parameters”

section for details) and set it up as Manual background (programmable) control.

3.Set up parameters: In “regulation mode”

Parameter Manual background , Manual background and Manual background .

Parameter Manual backgroundManual background can be set up when parameter Manual background is set as “0”.

Parameter Manual background and Manual backgroundManual background (control cycle for output 1) can be set up when parameter

Manual background is set as Manual background (heating) or Manual background (cooling) output. Manual background (control cycle for output 2)

can be set up when parameter Manual background is set as Manual background (heating) or Manual background (cooling) output.

Parameter Manual background and Manual backgroundCan be set up when parameter Manual background and Manual background are set as Manual background (heating) or Manual background (cooling) output. (The settings in Manual background and Manual background have to be different.)

Parameter Manual background and Manual background (in “operation mode")Can be set up when parameter Manual background is

set as Manual background or Manual background .

For Proportional Output Application: In this application, output 1 has to be analog output.

1.Set up output function: Enter parameter Manual background in “initial setting mode” (see “Setting up Parameters”

section for details) and set it as Manual background (proportional) output.

2.Set up parameters: In “regulation mode”

Parameter Manual background

For Upper/Lower Limits of Control Output:

1.Set up upper limit: Enter parameter Manual background in “regulation mode” (see “Setting up Parameters”

section for details). Range: Lower limit ~ 100%.

2.Set up lower limit: Enter parameter Manual background in “regulation mode” (see “Setting up Parameters”

section for details). Range: 0 ~ upper limit %.

For Alarm Application:

1. Set up output function (only when there is group INB): Enter parameter Manual background in “initial setting

mode” (see “Setting up Parameters” section for details) and set it as Manual background (alarm) output.

2.Set up alarm type: Enter parameter Manual background (with INB) or Manual background and Manual background (without INB) in “initial setting mode”. See Table 2 for more details on the alarm output.

3.Set up parameters: In “operation mode”

Parameter Manual background and Manual backgroundCan be set up when there is group INB.

Parameter Manual background , Manual background , Manual background and Manual backgroundCan be set up when there is no group INB.

4.Set up delay alarm output: Enter parameter Manual background in “regulation mode” (unit: second). The alarm will be enabled only when the temperature reaches the alarm output condition, and the condition remains until the delay time is reached.

DTE main unit offers 2 groups of alarm output, each with 12 alarm modes in the initial setting mode. When SV is higher or lower than SV, the alarm output will be enabled. See the table in the next column for the explanations on the 12 alarm output modes.

Note: AL-H and AL-L include AL1H, AL2H and AL1L, AL2L.

 

SV

 

Alarm Mode

 

Alarm Output Operation

0

 

No alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

Alarm output is enabled when the temperature reaches upper

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

and lower limits: The alarm will be enabled when PV exceeds

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV + AL-H or falls below SV – A L-L.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-L

SV

AL-H

 

 

 

Alarm output will be enabled when the temperature reaches the

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

upper limit: The alarm will be enabled when PV exceeds SV +

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-H.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV

AL-H

 

 

 

Alarm output will be enabled when the temperature reaches the

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

lower limit: The alarm will be enabled when PV falls below SV –

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A L-L.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-L

SV

 

 

 

 

4

 

Alarm output will be enabled when PV is between SV + AL-H

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and SV – AL-L.

 

 

 

AL-L

SV

AL-H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm output will be enabled when the temperature reaches the

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

absolute value of the upper and lower limits: The alarm will be

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

enabled when PV exceeds AL-H or falls below AL-L.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-L

 

 

AL-H

 

 

 

Alarm output will be enabled when the temperature reaches the

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

absolute value of the upper limit: The alarm will be enabled

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

when PV exceeds AL-H.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-H

 

 

 

Alarm output will be enabled when the temperature reaches the

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

absolute value of the lower limit: The alarm will be enabled when

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PV falls below AL-L.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-L

 

 

 

 

 

 

 

 

 

Upper/lower limit standby alarm: The alarm will be enabled when

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

PV reaches SV and further exceeds SV + AL-H or falls below

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV – AL –L.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-L

SV

AL-H

9

 

Upper limit standby alarm: The alarm will be enabled when PV

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reaches SV and further exceeds SV + AL-H.

 

 

 

 

 

 

 

SV

AL-H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

Lower limit standby alarm: The alarm will be enabled when PV

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reaches SV and further falls below SV – AL-L.

 

 

 

 

AL-L

SV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Upper limit hysteresis alarm: The alarm will be enabled when PV

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

exceeds SV + AL-H. The alarm will be disabled when PV falls

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

below SV.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-L

SV

AL-H

 

 

 

Lower limit hysteresis alarm: The alarm will be enabled when PV

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

falls below SV – AL-L. The alarm will be disabled when PV

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

exceeds SV.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-L

SV

 

AL-H

Table 2

Setting up Communication

1.Set up communication: Enter parameter Manual background , Manual background , Manual background , Manual background , Manual background and Manual background in “initial setting mode” (see “Setting up Parameters” section for details) and select your desired communication settings.

2.DTE series temperature controller is able to set up or read communication settings through DTE-2DS.

Selecting Channel

1.Select channel: Enter parameter Manual background in “regulation mode” (see “Setting up Parameters” section for details) and select the channel to be monitored.

2.How does it work: DTE main unit has maximum 8 channels which can be connected to 8 input sensors at the same time. The 8 input channels belong to group INA and INB, each group with 4 input channels. INB is optional accessory; therefore if INB is not inserted in DTE, DTE will only show 4 channels.

Setting up Copy Function

1. Set up the function: Enter parameter Manual background in “initial setting mode” (see “Setting up Parameters”

section for details) and select the function you desire.

2.How does it work: The copy function allows a DTE main unit to copy its parameters (including the values set in the parameter and communication settings) to another DTE main unit through DTE-2DS. Follow the steps below:

a.Insert DTE-2DS into the DTE main unit to be copied. Enter parameter Manual background in “initial setting

mode” and select Manual background, and DTE-2DS will read the parameters in the DTE main unit. Next, you

will see Manual background on the screen, indicating that the copy is successful. Manual background indicates the copy

fails. Press Manual background to return to “operation mode” and you will see the present temperature value (PV) and set temperature value (SV).

b.Switch off DTE and withdraw DTE-2DS. Insert DTE-2DS into another DTE main unit. Enter

parameter Manual background in “initial setting mode” and select Manual background . DTE-2DS will write the

parameters into it. Next, you will see Manual background on the screen, indicating that the writing-in is

successful. Manual background indicates the writing-in fails. Press Manual background to return to “operation mode” and you will see the present temperature value (PV) and set temperature value (SV).

Locking the Keys on Panel

1.Lock the keys: Enter parameter Manual background in “operation mode” (see “Setting up Parameters” section for details) and select the function you desire.

2.How does it work: Manual background indicates locking all the keys on the panel. Manual background indicates that you can only modify the set temperature value (SV), and all other functions are locked.

3.Press Manual background and Manual background at the same time to unlock the keys.

Analog Output & Temperature Tuning

1.Set up analog output tuning: Enter parameter Manual background and Manual background in “regulation mode” (see “Setting up Parameters” section for details) and tune the parameter to the desired output value.

2.Temperature offset tuning: Enter parameter Manual background in “regulation mode” and tune the parameter to the displayed temperature value.

3.How does it work:

a.Tuning analog output: For example, if you would like to have accurate 4 ~ 20mA of output, you can set up output 0% by manual control, connect the output to ampere meter and tune

parameter Manual background making the meter point to 4mA. Next, set up output 100% by manual control

and tune parameter Manual background making the meter point to 20mA.

b.Tuning temperature offset: This allows the displayed temperature to plus or minus 1 offset value.

Error Message

Error

 

PV

 

 

SV

Input sensor not connected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Internal communication error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Storage error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Channel disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Channel being initialized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

How to Install

1 Remove all the terminal blocks on the panel. 2 Uncover the panel and insert DTE-2DS to the “operation interface” slot.

3 Cover up the panel.

4 Insert the terminal blocks back to their

 

positions.

The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most updated version at http://www.delta.com.tw/industrialautomation

Page 2
Image 2
Delta Electronics DTE-2DS Setting up Communication, Selecting Channel, Setting up Copy Function, Locking the Keys on Panel