Parameter

 

 

 

and

 

 

 

 

 

 

can be set up when parameter

 

 

 

 

is set as “0”.

 

 

 

 

 

 

 

 

 

 

is not “0”.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

can be set up when

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

and

 

 

 

 

 

 

(control cycle for output 1) can be set up when parameter

 

is set as

 

 

 

 

(heating) or

 

 

 

(cooling) output.

 

 

 

(control cycle for output 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is set as

 

(heating) or

 

 

 

 

 

(cooling) output.

can be set up when parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

and

 

 

 

Can be set up when parameter

 

 

 

and

 

 

 

are set as

 

(heating) or

 

 

 

 

 

(cooling) output. (The settings in

 

and

 

 

 

have to be

 

 

 

 

 

 

 

 

 

 

different.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For ON/OFF Control Application:

1.Set up 2 outputs: Enter parameter and in “initial setting mode” (see “Setting up

Parameters” section for details). Set up one of the two parameters as or of control output.

2.Set up control type: Enter parameter in “initial setting mode” (see “Setting up Parameters”

section for details) and set it up as (ON/OFF) control.

3.Set up parameters: In “regulation mode”

Parameters and (hysteresis for output 1) can be set up when parameter is set as (heating) (cooling) output. (hysteresis for output 2) can be

set up when parameter is set as (heating) or (cooling) output. You can

only set up when and are set as or at the same time.

Parameter Can be set up when parameter and are set as control output,

and the settings in and are different, e.g. output 1 is (heating), and output

2 is (cooling).

For Manual Control Application:

1.Set up 2 outputs: Enter parameter and in “initial setting mode” (see “Setting up

Parameters” section for details). Set up one of the two parameters as or of control output.

2.Set up control type: Enter parameter in “initial setting mode” (see “Setting up Parameters”

section for details) and set it up as (manual) control.

3.Set up parameters: In “regulation mode”

Parameter and (control cycle for output 1) can be set up when parameter is set as (heating) or (cooling) output. (control cycle for output 2)

can be set up when parameter is set as (heating) or (cooling) output.

Parameter and (in “operation mode”) can be set up when parameter

is set as (heating) or (cooling) output. can be set up when

parameter is set as (heating) or (cooling) output.

For Programmable PID Application:

1.Set up 2 outputs: Enter parameter and in “initial setting mode” (see “Setting up

Parameters” section for details). Set up one of the two parameters as or of control output.

2.Set up control type: Enter parameter in “initial setting mode” (see “Setting up Parameters”

section for details) and set it up as (programmable) control.

3.Set up parameters: In “regulation mode”

Parameter , and .

Parameter can be set up when parameter is set as “0”.

Parameter and (control cycle for output 1) can be set up when parameter

is set as (heating) or (cooling) output. (control cycle for output 2)

can be set up when parameter is set as (heating) or (cooling) output.

Parameter and Can be set up when parameter and are set as (heating) or (cooling) output. (The settings in and have to be different.)

Parameter and (in “operation mode")Can be set up when parameter is

set as or .

For Proportional Output Application: In this application, output 1 has to be analog output.

1.Set up output function: Enter parameter in “initial setting mode” (see “Setting up Parameters”

section for details) and set it as (proportional) output.

2.Set up parameters: In “regulation mode”

Parameter

For Upper/Lower Limits of Control Output:

1.Set up upper limit: Enter parameter in “regulation mode” (see “Setting up Parameters”

section for details). Range: Lower limit ~ 100%.

2.Set up lower limit: Enter parameter in “regulation mode” (see “Setting up Parameters”

section for details). Range: 0 ~ upper limit %.

For Alarm Application:

1. Set up output function (only when there is group INB): Enter parameter in “initial setting

mode” (see “Setting up Parameters” section for details) and set it as (alarm) output.

2.Set up alarm type: Enter parameter (with INB) or and (without INB) in “initial setting mode”. See Table 2 for more details on the alarm output.

3.Set up parameters: In “operation mode”

Parameter and Can be set up when there is group INB.

Parameter , , and Can be set up when there is no group INB.

4.Set up delay alarm output: Enter parameter in “regulation mode” (unit: second). The alarm will be enabled only when the temperature reaches the alarm output condition, and the condition remains until the delay time is reached.

DTE main unit offers 2 groups of alarm output, each with 12 alarm modes in the initial setting mode. When SV is higher or lower than SV, the alarm output will be enabled. See the table in the next column for the explanations on the 12 alarm output modes.

Note: AL-H and AL-L include AL1H, AL2H and AL1L, AL2L.

 

SV

 

Alarm Mode

 

Alarm Output Operation

0

 

No alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

Alarm output is enabled when the temperature reaches upper

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

and lower limits: The alarm will be enabled when PV exceeds

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV + AL-H or falls below SV – A L-L.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-L

SV

AL-H

 

 

 

Alarm output will be enabled when the temperature reaches the

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

upper limit: The alarm will be enabled when PV exceeds SV +

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-H.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV

AL-H

 

 

 

Alarm output will be enabled when the temperature reaches the

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

lower limit: The alarm will be enabled when PV falls below SV –

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A L-L.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-L

SV

 

 

 

 

4

 

Alarm output will be enabled when PV is between SV + AL-H

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and SV – AL-L.

 

 

 

AL-L

SV

AL-H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm output will be enabled when the temperature reaches the

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

absolute value of the upper and lower limits: The alarm will be

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

enabled when PV exceeds AL-H or falls below AL-L.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-L

 

 

AL-H

 

 

 

Alarm output will be enabled when the temperature reaches the

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

absolute value of the upper limit: The alarm will be enabled

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

when PV exceeds AL-H.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-H

 

 

 

Alarm output will be enabled when the temperature reaches the

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

absolute value of the lower limit: The alarm will be enabled when

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PV falls below AL-L.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-L

 

 

 

 

 

 

 

 

 

Upper/lower limit standby alarm: The alarm will be enabled when

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

PV reaches SV and further exceeds SV + AL-H or falls below

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV – AL –L.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-L

SV

AL-H

9

 

Upper limit standby alarm: The alarm will be enabled when PV

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reaches SV and further exceeds SV + AL-H.

 

 

 

 

 

 

 

SV

AL-H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

Lower limit standby alarm: The alarm will be enabled when PV

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reaches SV and further falls below SV – AL-L.

 

 

 

 

AL-L

SV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Upper limit hysteresis alarm: The alarm will be enabled when PV

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

exceeds SV + AL-H. The alarm will be disabled when PV falls

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

below SV.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-L

SV

AL-H

 

 

 

Lower limit hysteresis alarm: The alarm will be enabled when PV

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

falls below SV – AL-L. The alarm will be disabled when PV

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

exceeds SV.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-L

SV

 

AL-H

Table 2

Setting up Communication

1.Set up communication: Enter parameter , , , , and in “initial setting mode” (see “Setting up Parameters” section for details) and select your desired communication settings.

2.DTE series temperature controller is able to set up or read communication settings through DTE-2DS.

Selecting Channel

1.Select channel: Enter parameter in “regulation mode” (see “Setting up Parameters” section for details) and select the channel to be monitored.

2.How does it work: DTE main unit has maximum 8 channels which can be connected to 8 input sensors at the same time. The 8 input channels belong to group INA and INB, each group with 4 input channels. INB is optional accessory; therefore if INB is not inserted in DTE, DTE will only show 4 channels.

Setting up Copy Function

1. Set up the function: Enter parameter in “initial setting mode” (see “Setting up Parameters”

section for details) and select the function you desire.

2.How does it work: The copy function allows a DTE main unit to copy its parameters (including the values set in the parameter and communication settings) to another DTE main unit through DTE-2DS. Follow the steps below:

a.Insert DTE-2DS into the DTE main unit to be copied. Enter parameter in “initial setting

mode” and select , and DTE-2DS will read the parameters in the DTE main unit. Next, you

will see on the screen, indicating that the copy is successful. indicates the copy

fails. Press to return to “operation mode” and you will see the present temperature value (PV) and set temperature value (SV).

b.Switch off DTE and withdraw DTE-2DS. Insert DTE-2DS into another DTE main unit. Enter

parameter in “initial setting mode” and select . DTE-2DS will write the

parameters into it. Next, you will see on the screen, indicating that the writing-in is

successful. indicates the writing-in fails. Press to return to “operation mode” and you will see the present temperature value (PV) and set temperature value (SV).

Locking the Keys on Panel

1.Lock the keys: Enter parameter in “operation mode” (see “Setting up Parameters” section for details) and select the function you desire.

2.How does it work: indicates locking all the keys on the panel. indicates that you can only modify the set temperature value (SV), and all other functions are locked.

3.Press and at the same time to unlock the keys.

Analog Output & Temperature Tuning

1.Set up analog output tuning: Enter parameter and in “regulation mode” (see “Setting up Parameters” section for details) and tune the parameter to the desired output value.

2.Temperature offset tuning: Enter parameter in “regulation mode” and tune the parameter to the displayed temperature value.

3.How does it work:

a.Tuning analog output: For example, if you would like to have accurate 4 ~ 20mA of output, you can set up output 0% by manual control, connect the output to ampere meter and tune

parameter making the meter point to 4mA. Next, set up output 100% by manual control

and tune parameter making the meter point to 20mA.

b.Tuning temperature offset: This allows the displayed temperature to plus or minus 1 offset value.

Error Message

Error

 

PV

 

 

SV

Input sensor not connected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Internal communication error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Storage error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Channel disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Channel being initialized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

How to Install

1 Remove all the terminal blocks on the panel. 2 Uncover the panel and insert DTE-2DS to the “operation interface” slot.

3 Cover up the panel.

4 Insert the terminal blocks back to their

 

positions.

The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most updated version at http://www.delta.com.tw/industrialautomation

Page 2
Image 2
Delta Electronics DTE-2DS Setting up Communication, Selecting Channel, Setting up Copy Function, Locking the Keys on Panel

DTE-2DS specifications

Delta Electronics, a global leader in power and thermal management solutions, has recently introduced the DTE-2DS, a highly advanced device designed for a variety of industrial and commercial applications. This cutting-edge solution exemplifies Delta's commitment to innovation, efficiency, and sustainable practices.

One of the standout features of the DTE-2DS is its ability to deliver exceptional energy efficiency. Equipped with a state-of-the-art digital signal processor (DSP), the device optimizes power consumption while maintaining peak performance. This ensures that businesses can significantly reduce their operational costs while complying with stringent energy regulations.

The DTE-2DS is designed with versatility in mind. Its modular architecture allows for easy scalability, making it suitable for various applications, from small manufacturing units to large industrial setups. This flexibility is complemented by the device's compatibility with different voltage levels and power ratings, enabling users to tailor it to their specific needs.

In terms of connectivity, the DTE-2DS is equipped with advanced communication interfaces, including Ethernet, RS-485, and Modbus, allowing for seamless integration into existing systems. This connectivity enhances remote monitoring and control capabilities, enabling operators to manage the device efficiently and gather real-time data for informed decision-making.

Another key characteristic of the DTE-2DS is its robust design, built to withstand harsh operating environments. The device features an IP65-rated enclosure, providing protection against dust and water ingress. This durability ensures reliability and longevity, even in challenging conditions.

Safety is paramount in the DTE-2DS design, with multiple protection features such as overload, overvoltage, and short-circuit protection. These safety mechanisms guarantee that the device operates securely, reducing the risk of damage to both the DTE-2DS and connected equipment.

Incorporating cutting-edge technologies such as advanced thermal management and smart control algorithms, the DTE-2DS maximizes performance while minimizing environmental impact. Delta Electronics’ commitment to sustainability is evident in this product, helping businesses transition to greener practices.

Overall, the Delta Electronics DTE-2DS stands out as a sophisticated solution that combines efficiency, flexibility, and reliability. Businesses seeking to optimize their energy use and enhance operational proficiency will find this device perfectly aligned with their goals.