bps. b0: 4800bps, b1: 9600bps, (factory setting) b2: 19200bps, b3: 38400 bps, b4: 57600 bps, b5:

115200 bps, b6-b13: reserved, b14: exchange low and high byte of CRC check code. (RTU mode

only) b15=0: ASCII mode, b15=1: RTU mode. Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1), while RTU mode is 8Bit, even bit, 1 stop bit (8 E 1).

10.CR#33 is used to set the internal function priority. For example: characteristic register. Output latched function will save output setting to the internal memory before power loss.

11.CR#34 is software version of model type.

12.CR#35~ CR#48 are used for system.

13.The corresponding parameters address H4032~H4063 of CR#0~CR#48 are provided for user to read/write data via RS-485.

A.Communication baud rate: 4800, 9600, 19200, 38400, 57600, 115200 bps.

B.Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1). Communication format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1).

C.Function code: 03H—read data from register. 06H—write one WORD to register. 10H—write multiple WORD to register.

5

ADJUST D/A CONVERSION CHARACTERISTIC CURVE

5.1Adjust D/A Conversion Characteristic Curve

Voltage output mode:

10V

 

 

 

Mode 0 of CR#1: GAIN = 5V(2000LSB),

 

mode 1

 

OFFSET=0V (0LSB)

 

 

 

 

 

Mode 1 of CR#1: GAIN = 6V(2400LSB),

 

 

 

 

 

 

 

mode 0

 

OFFSET=2V (800LSB).

 

 

 

GAIN:

The setting range of voltage output value when

6V

GAIN

 

 

5V

 

 

 

digital input value is K2000 should be

 

 

 

 

 

 

 

 

 

voltage

 

 

 

OFFSET:

-4V~+20V(-1600LSB~+8000 LSB).

output

 

 

 

The setting range of voltage output value when

2V

 

 

 

 

digital input value is K0 should be

0

 

+2000

+4000

 

-5V~+5V(-2000LSB~ +2000 LSB).

OFFSET

GAINOFFSET: Setting range: +1V~+15V (+400LSB ~ +6000 LSB).

Digital input

Current output mode

 

20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mode 2 of CR#1: GAIN = 12mA (2400LSB),

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mode 2

 

 

 

OFFSET=4mA (800LSB).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mode 3 of CR#1: GAIN = 10mA (2000LSB),

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mode 3

 

 

OFFSET=0mA (0LSB).

 

10mA

GAIN

 

 

GAIN:

The setting range of current output when digital

 

12mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

input value is K2000 should be -8mA~+40mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(-1600LSB~+8000LSB).

output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFFSET:

The setting range of current output when digital

 

4mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

input value is K0 should be -10mA ~+10mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(-2000LSB~+2000LSB).

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFFSET +2000

+4000 GAINOFFSET: Setting range: +2mA~+30mA (+400LSB

 

 

 

digital input

~+6000LSB).

 

The charts above are D/A conversion characteristic curve of voltage input mode and current input

6

INITIAL PLC START-UP

 

Lamp display

1.When power is on, POWER LED will be lit and ERROR LED will be lit for 0.5 second.

2.It is normal that POWER LED should be lit and ERROR LED should turn off. When power supply is lower than 19.5V, ERROR LED will blink continuously till the power voltage is higher than 19.5V.

3.When it connects to PLC MPU in series, RUN LED on MPU will be lit and A/D LED or D/A LED should blink.

4.After receiving the first RS-485 command during controlling via RS-485, A/D LED or D/A LED should blink.

5.After converting, ERROR LED should blink if input or output exceeds the upper bound or below

the lower bound. Program example:

M1000

 

FROM

K1

K0

D0

K1

 

 

 

 

CMP

H89

D0

M0

 

M1013

 

 

 

 

 

 

 

 

INC

D100

 

 

 

 

 

ADD

D101

K5

D101

 

LD=

K4000

D100

RST

D100

 

 

LD=

K4000

D101

RST

D101

 

 

M1

 

TO

K1

K1

H10

K1

 

 

M1

 

TO

K1

K6

D100

K2

 

 

 

 

END

 

 

 

 

Explanation:

Read the data of model type from expansion module K1 and distinguish if the data is H89 (DVP04DA-S model type).

D100 will increase K1 and D101 will increase K5 every second. When value of D100 and D101 attain to K4000, they will be reset to 0.

If the model type is DVP04DA-S, M1 will be on and set the output mode: CH1 mode to 0, CH2 mode to 2.

Writing output setting CR#6 and CR#7 to D100 and D101. Analog output will vary with D100 and D101 value.

7

COMMAND EXPLANATION

API

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Read special module

Adaptive model

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

API

 

TO

 

Special module CR

Adaptive model

79

D

P

data write in

 

ES

 

EP EH

 

 

 

 

 

 

 

Bit device

 

Word device

 

F 16-bit command (9 STEPS)

 

 

 

X Y M S K H KnX KnY KnM KnS T C D

E

 

Pulse

m1

 

 

¼ ¼

 

 

TO

Continuous

TOP

 

 

 

 

 

execution

 

execution

m2

 

 

¼ ¼

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

 

 

¼ ¼ ¼ ¼ ¼ ¼ ¼ ¼ ¼ ¼ ¼ 32-bit command (17 STEPS)

 

n

 

 

¼ ¼

 

 

DTO

Continuous

DTOP

Pulse

 

Note: The usage range of operand m1 is 0~7.

execution

execution

 

 

The usage range of operand m2: ES/EP:

Flag: When M1083 on, it allows to

 

 

0-48, EH: 0-254.

 

 

enable the interrupt during

 

 

The usage range of operand n: ES/EP:

 

FROM/TO. Refer to below for

 

 

1~(49-m2), EH: 1~(255-m2).

 

 

detail.

 

 

 

 

 

For ES series, it doesn’t support pulse

 

 

 

 

 

 

 

execution command (TOP, DTOP)

 

 

 

 

 

 

Command

 

: the number of special module.

: the number of CR (Control Register) of

Explanation

 

special module that will be wrote in.

 

: the data to write in CR.

: the data

 

 

 

number to write in one time.

 

 

 

 

 

 

 

 

 

DVP-series PLC uses this command to write data into CR of special module.

 

 

 

: When assigning bit operand, K1~K4 can be used for 16-bit and K5~K8 can be

 

 

 

used for 32-bit.

 

 

 

 

 

 

Program

 

Use 32-bit command DTO, program will write D11 and D10 to CR#3 and CR#2 of

Example

 

special module#0. It only writes one group of data in one time when=1.

 

 

 

 

 

Command will be executed when X0=ON, will not be executed when X0=OFF. The

 

 

 

previous write data won’t be changed.

 

 

 

 

 

 

 

 

 

X0

 

 

 

 

 

 

 

 

 

 

DTO

K0

K2

D0

K1

 

 

The rule of command operand

Footnotem1: arrangement number of special module. The number of special module that connects to PLC MPU. The number sequence of special module from the closest to the furthest of MPU is from 0 to 7. 8 modules is the max and it won’t occupy I/O point.

m2: the number of CR. There are 49 CR (Control Register) with 16-bit each built-in memory in the special module. The number of CR uses decimal digital (#0~#48). All running status and setting values of special module have included.

FROM/TO command is used to read/write CR data 1pcs at a time, while DFROM/DTO command is used to read/write CR data 2pcs in one time.

Upper 16-bit Lower 16-bit

CR #10

CR #9

Specified CR number

The number of transmission groups n. The meaning of n=2 of 16-bit command and n=1 of 32-bit are the same.

mode. Users can adjust conversion characteristic curve by changing OFFSET values (CR#18~CR#21) and GAIN values (CR#24~CR#27) depend on application.

78 D

FROM

CR data

ES EP EH

P

 

Specified device Specified CR

Specified device Specified CR

LSB (Least Significant Bit): 1.voltage output: 1LSB=10V/4000=2.5mV. 2.current output: 1LSB=20mA/4000=5µA.

5.2 Program Example for Adjusting D/A Conversion Characteristics Curve

Example 1: Setting OFFSET value of CH1 to 0V(=K0LSB) and GAIN value is 2.5V(=K1000LSB).

Bit device

Word device

 

 

X Y M S K H KnX KnY KnM KnS T C D

E

F

m1

¼ ¼

 

 

m2

¼ ¼

 

 

D

¼ ¼ ¼ ¼ ¼ ¼

¼

¼

n

¼ ¼

 

 

16-bit command (9 STEPS)

Continuous

 

Pulse

FROM execution

FROMP

execution

32-bit command (17 STEPS)

 

DFROM Continuous DFROMP Pulse

D0

 

 

CR #5

 

D1

 

 

CR #6

 

D2

 

 

CR #7

 

D3

 

 

CR #8

 

D4

 

 

CR #9

 

D5

 

 

CR #10

 

 

 

 

 

D0

CR #5

D1

CR #6

D2

CR #7

D3

CR #8

D4

CR #9

D5

CR #10

M1002

K1

K1

H10

K1

TO

Writing H10 to CR#1 of analog output module#0. Setting CH1 to mode 0 (voltage output 0V~ +10V) and CH2 to

Note: The usage range of operand m1 is 0~7. The usage range of operand m2: ES/EP: 0-48, EH: 0-254.

execution

execution

Flag: When M1083 on, it allows enable the interrupt during FROM/TO.

16-bit command when n=6

32-bit command when n=3

TO

K1

K33

H0

K1

X0

K1

K18

K0

K1

TO

mode 2 (current output 4mA~ +20mA).

Writing H0 to CR#33 and allow CH1 ~ CH4 to adjust characteristic.

When X0 switches from Off to On,

The usage range of operand n: ES/EP: n=

1~(49-m2), EH: 1~(255-m2).

ES series model doesn’t support pulse execution command (FROMP, DFROMP).

Refer to following for detail.

In ES series models, flag M1083 is not provided. All interrupts (including external or internal interrupt subroutines) will be disabled when FROM/TO command is executed. Interrupts will be resumed after FROM/TO command complete. Please be advised FROM/TO command also can be executed in the interrupt subroutine.

TO

K1

K24 K1000

K1

K0LSB of OFFSET value will be written to CR#18 and K1000LSB of GAIN value will be written to CR#24.

Command

: the number for special module.

: the number of CR (Control Register) of

Explanation

special module that will be read.

: the location to save reading data.

: the

 

The function of the flag M1083 (FROM/TO mode exchange) provided in EP/EH series models:

A. When M1083=Off, all interrupts (including external or internal interrupt

Example 2: Setting OFFSET value of CH2 to 2mA (=K400 LSB) and GAIN value to 18mA (=K3600LSB).

data number of reading ONCE.

DVP-series PLC uses this command to read CR data of special module.

subroutines) will be disabled when FROM/TO command is executed. The

Interrupts will resumed after FROM/TO command complete. Please be

M1002

K1

K1

H18

K1

TO

TO

K1

K33

H0

K1

X0

K1

K19

K400

K1

TO

TO

K1

K25

K3600

K1

Writing H10 to CR#1 of analog output module#0. Setting CH1 to mode 0 (voltage output 0V~ +10V) and CH2 to mode 3 (current output 0mA~ +20mA).

Writing H0 to CR#33 and allow CH1 ~ CH4 to adjust characteristic.

When X0 switches from Off to On, K400LSB of OFFSET value will be written to CR#19 and K3600LSB of GAIN value will be written to CR#25.

: When assign the bit operand, K1~K4 are used for 16-bit and K5~K8 are used for

 

32-bit.

 

Please refer the footnote below for calculation the special module number.

Program

Read the content of CR#24 of special module#0 save it to D0 of PLC, and read the

Example

content of CR#25 of special module#0 save it to D1 of PLC. 2 data are read in one

 

time when n=2.

Command will be executed when X0=ON. Command won’t be executed if X0=OFF and the content of previous reading data won’t change.

X0

FROM K0

K24

D0

K2

advised FROM/TO command can be executed in the interrupt subroutine.

B. When M1083=On, if an interrupt enable occurs while FROM/TO command

are executing, the interrupt FROM/TO command will be blocked till the

requested interrupt finish. Unlike M1080 off situation, FROM/TO command

cannot be executed in the interrupt subroutine.

Page 2
Image 2
Delta Electronics DVP04DA-S Adjust D/A Conversion Characteristic Curve, Initial PLC START-UP, Command Explanation