AlphaServer 8400

Specifications

Physical Characteristics

Operating

 

Shipping

Height

170.0 cm (67.0 in.)

 

195.0 cm (76.7 in.)

Width

80.0 cm (31.5 in.)

 

109.5 cm (43.1 in.)

Depth

87.5 cm (34.4 in.)

 

121.0 cm (47.5 in.)

Weight, full configuration

 

 

 

 

Without batteries

408 kg (900 lb.)

 

448 kg (1000 lb.)

With batteries

545 kg (1200 lb.)

 

585 kg (1300 lb.)

Clearances

Operating

 

Service

 

 

 

 

Front

1.0 m (40 in.)

 

1.5 m (59 in.)

Rear

1.0 m (40 in.)

 

1.0 m (40 in.)

Sides

0

 

0

 

Environmental

Operating

 

Non-Operating

 

 

￿￿

Temperature

15° to 28°C (59° to 82°F)

40° to 66°C ( 40° to 151°F)

Humidity

20% to 80%

 

10% to 95%

Altitude

0 2.4 km (0￿8000 ft)

9,100 m (30,000 ft)

Vibration

2￿22 Hz @ 0.01"da minimum

22￿500 Hz @ 0.25g max.

Heat dissipation1

Minimally configured system1

 

 

 

(system cabinet)

 

 

 

 

3,400 Btu/hr, 1,000 W

 

 

 

Fully configured system2

 

 

 

(system cabinet)

 

 

 

 

15,700 Btu/hr, 4,600 W

 

 

 

Fully configured system3

 

 

 

(system cabinet with two

 

 

 

I/O expansion cabinets)

 

 

 

30,600 Btu/hr, 9,000 W

 

 

Regulatory

 

 

 

 

 

 

 

 

Agency approvals

UL Listed to UL1950

 

 

 

UL Classified to IEC950

 

 

 

CSA Certified to CAN/CSA-C22.2, No. 950-M89

 

FCC Part 15 (Class A)

 

 

 

CE Declaration #1171

 

 

Reviewed to

AS 3260, Australian Standard

 

 

 

EN 60950, European Norm

 

 

Power Requirements1

 

 

 

 

Three-Phase Power Subsystem2

US/Canada

Europe/AP

 

Japan

Nominal voltage

120/208 V

380￿415 V

 

202 V

Frequency range

50￿60 Hz

50￿60 Hz

 

50￿60 Hz

Phases

3-phase star

3-phase star

 

3-phase delta

 

4-wire N-GND

4-wire N-GND

4-wire mid-GND or

 

 

 

 

3-wire junction GND

Maximum input current/phase

24 A rms

12.8 A rms

 

24 A rms

Surge current

50 A peak

50 A peak

 

50 A peak

Rating

30 A

16 A

 

30 A

Power cap (system)

DEC 12-12314-00

DEC 12-30333-02

DEC 12-12314-00

Receptacle (site)

DEC 12-12315-01

See footnote 4

DEC 12-12315-01

(Industry equivalent)

NEMA L21-30R

IEC 309

 

NEMA L21-30R

PCS/PDS/PDU/UPS cable

BC24W

BN29X

 

BC24W

1Minimally configured system contains one regulator, one CPU module, one memory module, one KFTIA-AA module, CD-ROM, and RZ28 disk drive.

2Fully configured system contains two power regulators, four CPU modules, three memory modules, two System I/O modules, one DWLPB-AA, one DWLPB-BA, three BA655-AB, CD-ROM, 36 RZ28 drives.

3Fully configured system and expansion cabinets consist of the above “fully configured system” and two expansion cabinets which each contain one DWLPB-AB, one DWLPB-BB, six KZPSA-BB, five BA655-AB, and 60 RZ28 drives.

4Receptacle type is Hubbell 516R6 or equivalent

Alpha Servers 3.229

Page 24
Image 24
Key Digital 8400 warranty AlphaServer Specifications, Physical Characteristics Operating Shipping