The ESI 48/120V Inverter
Description:
The ESI 48/120V inverters are single phase, 
Features
•Standard 19” or 23” rack
•1KVA/800W, 2KVA/1600W
•Selectable 100V/110V/115V/120V system output
•High efficiency
•Pure sine wave output
•Compact, lightweight modular design
•Bypass function
•
•Optional SNMP Interface card
•User friendly LED and LCD display
Specification
| General | 
 | 
| Product name | ESI 48 / 120 V – 1k VA | 
| 
 | ESI 48 / 120 V – 2k VA | 
| Efficiency, at 120Vrms | 83 % | 
| Safety | UL 60950 | 
| 
 | |
| EMI, radiated compliant with | FCC Part 15 class A | 
| Cooling | Fan cooled | 
| On/Off Switch | Yes | 
| MTBF | 450K Hours | 
| DC Input | 
 | 
| Input voltage | 40 … 60 Vdc | 
| Rated current | 25 A (1k VA) / 50 A (2k VA) | 
| AC Input(Bypass) | 
 | 
| Input voltage | 100 / 110 / 115 / 120 Vrms ± 20 Vrms | 
| Frequency | 50 / 60 Hz ± 5 Hz | 
| EMI, conducted compliant with | FCC Part 15 class A | 
| Output | 
 | 
| Output voltage | 100 / 110 / 115 / 120 Vrms | 
| Voltage regulation | ± 3 % | 
| Frequency | 50 / 60 Hz ± 0.2 Hz | 
| THD | 3 %: 100% liner load | 
| 
 | 5 %: 100% SPS load | 
| Current, nominal | 10 Arms (1kVA) | 
| Crest factor | 20 Arm (2kVA) | 
| 3 : 1 | |
| Mechanics | 
 | 
| Width, overall | 17.3” / 440 mm | 
| Depth, overall | 11.8” / 300 mm | 
| Height, overall | 3.5” / 88.0 mm | 
| Weight | 15.4 lb / 7 kg (1k VA); 17.6 lb / 8 kg (2k | 
| 
 | VA) | 
| Environment | 
 | 
| Operating temperature | 0 ... + 45 °C | 
| Relative humidity | 20 ~ 90 %, non condensing | 
| Altitude | - 500 ~ 10000 feet | 
*Specifications are subject to change.