OWNER’S MANUAL
INSTALLATION
Continued
7.Attach base assembly to fireplace floor using two masonry screws (in hardware package) (see Figure 12).
8.Connect to gas supply. See Connect- ing To Gas Supply.
Flexible Gas Hose (if allowed by local codes)
Fitting
Figure 11 - Attaching Flexible Gas Hose to Heater
Masonry Screw
Mounting
Flanges
Figure 12 - Attaching Base Assembly to Fireplace Floor
CONNECTING TO GAS SUPPLY
WARNING: This appliance re- quires a 1/2" NPT (National Pipe Thread) inlet connection to the pressure regulator.
WARNING: A qualified service person must connect heater to gas supply. Follow all local codes.
Installation Items Needed
Before installing heater, make sure you have the items listed below.
•piping (check local codes)
•sealant (resistant to propane/LP gas)
•equipment shutoff valve *
•test gauge connection *
•sediment trap
•tee joint
•pipe wrench
*An CSA
WARNING: Never connect heater to private
CAUTION: Use only new, black iron or steel pipe. Inter-
Approved Flexible Gas Hose (if allowed by local codes)
Gas
Control
Figure 13 - Gas Connection
Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 13).
IMPORTANT: Install equipment shutoff valve in an accessible location. The equip- ment shutoff valve is for turning on or shutting off the gas to the appliance.
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
CAUTION: Use pipe joint seal- ant that is resistant to liquid pe- troleum (LP) gas.
We recommend that you install a sediment trap in supply line as shown in Figure 12. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sedi- ment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.
CAUTION: Avoid damage to regulator. Hold gas regulator with wrench when connecting it to gas piping and/or fittings.
CSA
From Gas Meter (5" W.C.** to 10.5" W.C. Pressure)
| Tee |
| |
3" Minimum | Joint | Sedi- | |
Pipe | |||
ment | |||
| |||
| Nipple | ||
| Trap | ||
| Cap | ||
|
|
*Purchase the optional CSA
** Minimum inlet pressure for purpose of input adjustment. | Continued |
107553 | 11 | For more information, visit www.desatech.com |