INSTALLATION

Continued

INSTALLATION AND CLEARANCES FOR VENT-FREE OPERATION

WARNING: Maintain the mini- mum clearances. If possible, pro- videgreaterclearancesfromfloor, ceiling, and adjoining wall.

LOG SIZING REQUIREMENTS

Log

Minimum Firebox

 

Size

Height

Depth

Front

Rear *

 

 

 

Width

Width

24"

17"

14"

28"

20 1/4"

 

Minimum Firebox with Blower

 

 

 

 

 

24"

17"

14"

34"

22 3/8"

* Measured at 14" depth.

Carefully follow the instructions below. This will ensure safe installation into a masonry, UL127-listed manufactured fireplace, or listed vent-free firebox.

Minimum Clearances For Side Combustible Material, Side Wall, and Ceiling

A.Clearances from the side of the fireplace cabinet to any combustible material and wall should follow diagram in Figure 4.

Example: The face of a mantel, bookshelf, etc. is made of combustible material and protrudes 3 1/2" from the wall. This combus- tible material must be 4" from the side of the fireplace cabinet (see Figure 4).

Note: When installing your gas logs into a manufactured firebox, follow firebox manufacturerʼs instructions for minimum clearances to combustible materials.

B.Clearances from the top of the fireplace opening to the ceiling should not be less than 42 inches.

Example

*

*Minimum 16 inches from Side Wall

Figure 4 - Minimum Clearance for

Combustible to Wall

Minimum Noncombustible Material Clearances

If Not Using Mantel

Note: If using a mantel proceed to If Using Mantel. If not using a mantel, follow the information on this page.

You must have noncombustible material(s) above the fireplace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible material must extend at least 8" up. If noncombustible material is less than 12", you must install the fireplace hood ac- cessory. See Figure 5 for minimum clearances.

If Using Mantel

You must have noncombustible material(s) above the fireplace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombus- tible material must extend at least 8 inches up. If noncombustible material is less than 12", you must install the fireplace hood accessory. Even if noncombustible material is more than 12", you may need the hood accessory to deflect heat away from your mantel shelf. See Figure 5 and Figures 6 and 7, page 10, for minimum clearances.

IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open.

Noncombustible

Requirements for

Material Distance (A)

Safe Installation

12" or more

Noncombustible material

 

okay.

Between 8"

Install fireplace hood

and 12"

accessory (GA6050,

 

GA6052, or GA6053 see

 

Accessories, page 25).

Less than 8"

Noncombustible material

 

must be extended to at

 

least 8". See Between 8"

 

and 12", above. If you

 

cannot extend material,

 

you must operate heater

 

with flue damper open.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 5 - Heat Resistant Material (Slate,

Marble, Tile, etc.) Above Fireplace

113183-01B

www.desatech.com

9

Page 9
Image 9
Desa CDR3924NT installation manual Installation and Clearances for VENT-FREE Operation, Log, Rear, Width