Desa installation manual Checking GAS Connections, Pressure Testing Gas Supply Piping system

Models: CGD3018N, CGD3924N, CGD3930N, CRL2718N, CCL3924N, CRL3124N, CCL3018N, CGD3924NT, CGD3018NT, CCL3924NT, CGD3930NT, CCL3018NT, CCL3930NTA

1 40
Download 40 pages 44.81 Kb
Page 12
Image 12

12

INSTALLATION

Connecting To Gas Supply (Cont.) Checking Gas Connections

INSTALLATION

Continued

Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 15).

IMPORTANT: Install equipment shutoff valve in an accessible location. The equipment valve is for turning on or shutting off the gas to the appliance.

Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.

WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

We recommend that you install a sediment trap in supply line as shown in Figure 15. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

CAUTION: Avoid damage to regulator. Hold gas regulator with wrench when connecting it to gas piping and/or fittings.

From Gas Meter

CSA Design-Certified Equipment

Shutoff Valve With 1/8" NPT Tap*

(5" W.C.** to

 

10.5" W.C.

Approved Flexible

Pressure)

Gas Hose (if allowed

 

by local codes)

Tee

 

Joint

 

Pipe

3" Minimum

 

Nipple

Gas

 

Cap

Regulator

 

Sediment Trap

Figure 15 - Gas Connection

*Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 36.

**Minimum inlet pressure for purpose of input adjustment.

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections for leaks after installing or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping system

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping sys- tem. Pressures in excess of 1/2 psig will damage heater regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.

4.Check all joints of gas supply piping system. Apply a noncor- rosive leak detection fluid to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Reconnect heater and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 16).

2.Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.

3.Check all joints from gas meter to equipment shutoff valve (see Figure 17, page 13). Apply a noncorrosive leak detection fluid to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Open

Equipment

Shutoff Valve

Closed

Figure 16 - Equipment Shutoff Valve

For..com

107123-01F

Page 12
Image 12
Desa installation manual Checking GAS Connections, Pressure Testing Gas Supply Piping system

CGD3018N, CGD3924N, CGD3930N, CRL2718N, CCL3924N, CRL3124N, CCL3018N, CGD3924NT, CGD3018NT, CCL3924NT, CGD3930NT, CCL3018NT, CCL3930NTA specifications

The Desa product line, consisting of models CGD3018N, CGD3924N, CGD3930N, CRL2718N, CCL3924N, CRL3124N, CCL3018N, CGD3924NT, CGD3018NT, CCL3924NT, CGD3930NT, CCL3018NT, and CCL3930NTA, offers a wide range of heating solutions designed to tackle diverse customer needs. These models are distinctive for their durability, efficiency, and user-friendly designs.

Among the standout features of the Desa CGD series, models such as CGD3018N and CGD3924N integrate advanced combustion technologies that maximize fuel efficiency while minimizing emissions. This ensures that users enjoy a cleaner burn and reduced operational costs. The CGD3930N model boasts a higher output, making it suitable for larger spaces, while maintaining a compact design to fit various room layouts.

The CRL series, including CRL2718N and CRL3124N, emphasizes flexibility and ease of installation. These units employ a direct venting system that allows for efficient heat distribution without the need for extensive ductwork. The CCL models, such as CCL3924N and CCL3018N, are designed with aesthetics in mind. They feature sleek styles that blend seamlessly into modern home decors, all while delivering reliable heating performance.

The NT variants, such as CGD3924NT and CCL3924NT, introduce smart technology integration, allowing users to control their heating solutions remotely via smartphone applications. This feature ensures maximum convenience and adaptability to varying user preferences or schedules.

In terms of safety, all models are equipped with built-in features to prevent overheating and ensure stable operation. Additionally, many units incorporate easy-to-use thermostats and adjustable flame settings, providing users with greater control over their indoor climate.

Overall, the Desa models combine innovation with practicality, making them a preferred choice for consumers looking for efficient, stylish, and reliable heating solutions. With a variety of products catering to different preferences and requirements, Desa continues to be a leader in the heating industry, ensuring comfort and satisfaction for all users.