Desa CRN30 installation manual Test Pressures In Excess Of 1/2 Psig 3.5 kPa

Models: CRN30

1 32
Download 32 pages 45.03 Kb
Page 13
Image 13

INSTALLATION

Continued

PRESSURE TESTING GAS SUPPLY PIPING SYSTEM

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.

4.Check all joints of gas supply piping system. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Reconnect heater and equipment shutoff valve to gas supply. Check reconnected fit- tings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 16).

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.

3.Check all joints from gas meter for natural gas (see Figure 17) or propane/LP supply tank for propane/LP gas, to equipment shutoff valve (see Figure 18). Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

4.Correct all leaks at once.

PRESSURE TESTING HEATER GAS CONNECTIONS

1.Open equipment shutoff valve (see Figure 16).

2.For natural gas open main gas valve located on or near gas meter. For propane/LP gas open propane/LP supply tank valve.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from equipment shutoff valve to thermostat gas valve (see Figure 17 or 18). Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, page 14). Check all other internal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Ap- pliance, page 15 or 16 depending on your model).

8.Replace front panel.

Equipment

Open

 

Shutoff Valve

 

Closed

Figure 16 - Equipment Shutoff Valve

Thermostat Gas Valve

Gas

Meter

Equipment

Shutoff

Valve

Figure 17 - Checking Gas Joints for

Natural Gas

Thermostat Gas Valve

Propane/LP

Supply Tank

Equipment

Shutoff

Valve

Figure 18 - Checking Gas Joints for

Propane/LP Gas

107883-01H

www.desatech.com

13

Page 13
Image 13
Desa CRN30 Test Pressures In Excess Of 1/2 Psig 3.5 kPa, Test Pressures Equal To or Less Than 1/2 Psig 3.5 kPa