Desa FVF30N Connecting To Gas Supply, Unvented Natural Gas Log Heater, Installation, Continued

Models: FVF30N

1 24
Download 24 pages 31.09 Kb
Page 12
Image 12
CONNECTING TO GAS SUPPLY

UNVENTED NATURAL GAS LOG HEATER

INSTALLATION

Continued

CONNECTING TO GAS SUPPLY

Manual backgroundWARNING: A qualified service person must connect heater to gas supply. Follow all local codes.

Installation Items Needed

Before installing heater, make sure you have the items listed below.

piping (check local codes)

sealant (resistant to propane/LP gas)

equipment shutoff valve *

test gauge connection *

sediment trap

tee joint

pipe wrench

Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 13).

IMPORTANT: Install equipment shutoff valve in an accessible location. The equip- ment shutoff valve is for turning on or shutting off the gas to the appliance.

Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.

Manual backgroundCAUTION: Use pipe joint seal- ant that is resistant to liquid pe- troleum (LP) gas.

We recommend that you install a sediment trap in supply line as shown in Figure 13. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sedi- ment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

Manual background CAUTION: Avoid damage to regulator. Hold gas regulator with wrench when connecting it to gas piping and/or fittings.

CSA Design-Certified

Equipment shutoff Valve

With 1/8" NPT Tap

*A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Pur- chase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 21.

Manual background WARNING: Never connect heater to private (non-utility) gas wells. This gas is commonly known as wellhead gas.

From Gas Meter (5" W.C.** to 10.5" W.C. Pressure)

 

Tee Joint

 

Sediment

Pipe

 

Trap

Nipple

3" Minimum

 

Cap

 

Approved Flexible Gas Hose (if allowed by local codes)

Gas Regulator

Manual background CAUTION: Use only new, black iron or steel pipe. Inter- nally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to heater. If pipe is too small, undue loss of volume will occur.

Figure 13 - Gas Connection

* Minimum inlet pressure for purpose of input adjustment.

12

105191

Page 12
Image 12
Desa FVF30N installation manual Connecting To Gas Supply, Unvented Natural Gas Log Heater, Installation, Continued