UNVENTED NATURAL GAS LOG HEATER

AIR FOR COMBUSTION AND VENTILATION

Continued

VENTILATION AIR

Ventilation

Grills

Into Adjoining

12"

Ventilation Grills

Into Adjoining Room,

Room,

Or

Option 2

Ventilation Air From Inside

Option 1

Remove

Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro- vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see op- tion 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two per- manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/ NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventila- tion grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Door into Adjoining Room, Option 3

12"

Figure 2 - Ventilation Air from Inside Building

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

6

105191

Page 6
Image 6
Desa FVF30N installation manual Ventilation AIR, Ventilation Air From Inside, Building, Ventilation Air From Outdoors