INSTALLATION
Continued
The appliance gas inlet connection is 3/8" NPT at the regulator, located at the rear of the appliance.
Approved Flexible | CSA | |||
Gas Hose (If | ||||
Equipment Shutoff | Valve | |||
allowed by local | ||||
with 1/8" | NPT Tap* |
| ||
codes) |
| |||
|
|
|
IMPORTANT: Hold appliance regulator with a wrench to prevent movement when connecting to inlet piping.
CAUTION: Use only new, black iron or steel pipe. Inter-
3" Minimum
Natural From Gas Meter (5" W.C.** to 10.5" W.C. Pressure)
Installation must include an equipment shutoff valve, union and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from log set (see Figure 4).
IMPORTANT: Install equipment shutoff valve in an accessible location.The equipment shutoff valve is for turning on or shutting off the gas to the appliance.
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
Install a sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater
may not run properly.
|
| Propane/LP | |
Pipe Cap | Tee | From External | |
Regulator (11" | |||
Nipple | Joint | ||
W.C.** to 14" | |||
|
| ||
|
| W.C. Pressure) |
Figure 4 - Gas Connection
*Purchase the optional
** Minimum inlet pressure for purpose of input adjustment.
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping and connections for leaks after installing or servicing. Correct all leaks at once.
WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detec- tion fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1.Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator.
2.Cap off open end of gas pipe where equipment shutoff valve was connected.
3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.
www.desatech.com | 7 |