![MANTEL CLEARANCES FOR BUILT-IN INSTALLATION](/images/new-backgrounds/55051/5505119x1.webp)
®
UNVENTED PROPANE/LP GAS FIREPLACE
INSTALLATION
Continued
MANTEL CLEARANCES FOR BUILT-IN INSTALLATION
If placing mantel above
If your installation does not meet the above minimum clearances, you must:
• raise the mantel to an acceptable height,
OR
• remove the mantel.
Note: |
| Mantel Shelf | |||
10" |
|
|
|
| |
All Vertical |
|
|
|
| |
|
|
|
|
| |
measurements | 8" |
|
|
|
|
|
|
|
| ||
are from top of | 6" |
|
|
|
|
|
|
|
| ||
fireplace |
|
|
|
| |
2 1/2" |
|
|
|
| |
opening to |
|
|
|
| |
bottom of |
|
|
|
|
|
mantel shelf. |
|
|
|
|
|
Minimum Non- |
|
|
|
|
|
Combustible |
|
|
|
|
|
Material | 13" | 16" | 19" | 21" |
|
|
| ||||
|
|
|
|
|
|
Supplied Firebox
Hood Must Be
Used at All Times
Figure 16 - Minimum Mantel Clearances for
INSTALLING GAS PIPING TO FIREPLACE LOCATION
WARNING: This appliance re- quires a 1/2" NPT (National Pipe Thread) inlet connection to the pressure regulator.
WARNING: A qualified ser- vice person must connect fire- place to gas supply. Follow all local codes.
CAUTION: Never connect heater directly to the propane/ LP supply. This heater requires an external regulator (not sup- plied). Install the external regu- lator between the heater and pro- pane/LP supply.
Installation Items Needed
Before installing fireplace, make sure you have the items listed below.
•external regulator (supplied by installer)
•piping (check local codes)
•sealant (resistant to propane/LP gas)
•equipment shutoff valve *
•test gauge connection *
•sediment trap
•tee joint
•pipe wrench
*An CSA/AGA
The installer must supply an external regu- lator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incom- ing gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure
17.Pointing the vent down protects it from freezing rain or sleet.
Propane/LP
Supply Tank
External
Regulator
Vent
Pointing
Down
Figure 17 - External Regulator with Vent Pointing Down
CAUTION: Use only new, black iron or steel pipe. Inter-
Installation must include a equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 18).
IMPORTANT: Install equipment shutoff valve in an accessible location. The equip- ment shutoff valve is for turning on or shutting off the gas to the appliance.
Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves. Do not use sealant on flare threads.
CAUTION: Use pipe joint seal- ant that is resistant to liquid pe- troleum (LP) gas.
CSA/AGA Design-
Certified Equipment
Shutoff Valve With
1/8" NPT Tap*
Approved |
|
Flexible Gas |
|
Line |
|
| From External |
| Regulator |
| (11" W.C. to 14" |
3" Minimum | W.C. Pressure) |
|
Pipe Nipple Cap Tee Joint
Sediment Trap
Figure 18 - Gas Connection
10 | 104637 |