Desa VFRMV24NA, VFRMV18NA Installation, Minimum Noncombustible material Clearences, Continued

Models: VFRMV24NA VFRMV18NA VFRMV18PA

1 31
Download 31 pages 62 Kb
Page 8
Image 8
INSTALLATION

8

INSTALLATION

Installation and Clearences for Vent-free Operation (cont.)

INSTALLATION

Continued

Care fully follow the instructions below. This will ensure safe installation into masonary, UL127-listaed manufactured fireplace, or listed vent-free firebox.

Minimum Clearances For Side Combustible material, side wall, and ceiling

A. Clearances from the side of the fireplace cabinet to any combustible material and wall should follow diagram in figure 4.

Example: The face of a mantel, bookshelf, etc.. is made of combus- tible material must be 4" from the side of the fireplace to the cabinet (see figure 4).

B. Clearances from the top of the fireplace opening to the ceiling should not be less than 42 inches.

Example

*

*Minimum 16 inches from Side Wall

Figure 4 - Minimum Clearance for Combustible to Wall

NOTICE: Non thermostat controlled heaters maybe used as a vented product. If so, you must always run heater with chimney flue damper open, noncombustible material above the fireplace opening is not needed. Go to Installing Damper Clamp Accessory for vented operation.

Minimum Noncombustible material Clearences

If Not Using Mantel

Note: If using a mantel proceed to If Using Mantel. If not using mantel, follow the information on this page.

You must have non-combustible material(s) above the fireplace opening. Non-combustible materials (such as slate, marble, tile, etc..) Must be at least 1/2 inch thick. With sheet metal, you must have non-combustible material behind it. Non-combustible material must extend at least 8" up (for all models). If non-combustible material is less than 12", you must install the fireplace hood accessory (24" and 30" Models Only). See Figure 5 for minimum clearances.

If Using Mantel

You must have non-combustible material(s) above the fireplace opening. Non-combustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have non-combustible material behind it. Non-combustible material must extend at least 8 inches up (for all models). If non-combustible material is less than 12", you must install the fireplace hood accessory (24" Models Only). Even if non-combustible material is more than 12", you may need the hood accessory to deflect heat away from your mantel shelf. See Figure 5 and Figures 6 and 7, page 9, for minimum clearances.

IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 10.

Noncombustible

Requirements for

Material Distance (A)

Safe Installation

12" or more

Non-combustible material OK.

Between 8" and 12"

24" Models: Install fireplace hood acces-

 

sory (GA6060, see Accessories, page

 

27).

 

18" Model: Non-combustible material

 

OK.

Less than 8"

Non-combustible material must be extend-

 

ed to at least 8". See Between 8" and 12",

 

above. If you cannot extend material, you

 

must operate heater with flue damper

 

open.

 

 

Heat Resistant Continued

Material

(A)

Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.) Above Fireplace

Minimum Noncombustible material ClearencesManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundFor more information, visit www.desatech.comManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

114745-01

Page 8
Image 8
Desa VFRMV24NA, VFRMV18NA, VFRMV18PA installation manual Installation, Minimum Noncombustible material Clearences, Continued