INSTALLATION

Continued

CHECKING GAS CONNECTIONS

WARNING: Test all gas pip- ing and connections, internal and external to unit, for leaks after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.

3.Check all joints from gas meter to equipment shutoff valve for natural gas or propane/LP supply to equipment shutoff valve for propane/ LP (see Figures 19 and 20). Apply noncorro- sive leak detection fluid to all joints. Bubbles forming show a leak.

4.Correct all leaks at once.

open flame to check for a leak. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

Equipment Shutoff Valve

Open

Correct all leaks at once.

Closed

Figure 18 - Equipment Shutoff Valve

CAUTION: Make sure exter- nal regulator has been installed between propane/LPsupply and fireplace. See guidelines under Connecting Fireplace to Gas Supply, page 15.

PRESSURE TESTING GAS SUPPLY PIPING SYSTEM

Test Pressures In Excess Of 1/2 PSIG

Gas Control Valve

Equipment

Shutoff

Valve

Gas Meter

(3.5 kPa)

1.Disconnect fireplace with its main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage fireplace regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.

4.Check all joints of gas supply piping system. Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Reconnect fireplace and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1. Close equipment shutoff valve (see Figure 18).

Figure 19 - Checking Gas Joints for

Natural Gas

Equipment Shutoff Valve

Propane/LP

Supply Tank

Gas Control Valve

Figure 20 - Checking Gas Joints for

Propane/LP Gas

PRESSURE TESTING FIREPLACE GAS CONNECTIONS

1.Open equipment shutoff valve (see Figure 18).

2.Open main gas valve located on or near gas meter for natural gas or open propane/LP supply tank valve.

3.Make sure control knob of fireplace is in the OFF position.

16

www.desatech.com

116746-01A

Page 16
Image 16
Desa VSGF36NTA, VSGF36PRA, VSGF36PTA, VSGF36NRA Checking GAS Connections, Test Pressures In Excess Of 1/2 Psig, KPa

VSGF36NRA, VSGF36NTA, VSGF36PTA, VSGF36PRA specifications

Desa VSGF36PRA, VSGF36PTA, VSGF36NTA, and VSGF36NRA are various models from a contemporary line of gas fireplaces that combine aesthetics, functionality, and advanced technology to enhance residential spaces. Each model offers unique features and characteristics designed to meet different consumer needs and preferences.

The VSGF36PRA model stands out with its radiant heat and realistic flame display, effectively mimicking the experience of a traditional wood-burning fireplace. Its easy installation process makes it a viable choice for both new constructions and retrofitting existing spaces. The model utilizes high-efficiency gas burning technology, ensuring a warm and cozy environment while maintaining energy savings. Furthermore, it boasts a stylish design that can seamlessly integrate into any living room setting.

The VSGF36PTA is another dynamic addition to the lineup, featuring a traditional appearance with modern advancements. This model is known for its programmable thermostat that allows homeowners to control the temperature more precisely. The patented burner system creates a beautiful and lifelike flame, adding to the ambiance of any room. Additionally, the VSGF36PTA is equipped with a safety shut-off feature, ensuring peace of mind for users.

In contrast, the VSGF36NTA model targets those who appreciate a contemporary design. With its sleek lines and minimalistic facade, it offers an elegant touch to modern homes. This model incorporates advanced electronic ignition and a remote control for effortless operation, allowing users to enjoy their fireplace with convenience. The high-efficiency venting system also ensures optimal performance with lower emissions, making it environmentally friendly.

Lastly, the VSGF36NRA model combines both performance and versatility. This unit is designed for flexible installation options, allowing it to fit into various spaces. The customizable flame height and adjustable fan speed are key features that enhance the user experience. In terms of heating capabilities, the VSGF36NRA is engineered to provide reliable warmth during colder months while ensuring high efficiency.

Overall, the Desa VSGF36 series offers a diverse range of options suitable for various aesthetic preferences and functional needs. Each model features cutting-edge technology, ensuring that homeowners can enjoy the beauty and warmth of a fireplace while benefiting from enhanced efficiency and safety features.