Venting Installation

instructions

Continued

Note: Install restrictor into inner collar of fireplace as shown.

Vertical Venting

V = 40' max.

Note: Install restrictor into inner collar of fireplace as shown.

45° Elbow

45° Elbow

Venting with Two 90° Elbows

Vertical (V1)

Horizontal (H)

5' min.

6' max.

6' min.

12' max.

7' min.

18' max.

8' min.

20' max.

Note: Vertical (V1) + Vertical (V2) = 40' max.

Figure 23 - Vertical Venting

Configuration Using Two 90° Elbows

(Vertical Round High Wind Termination

Shown)

Figure 24 - Vertical Venting

Configuration With No Horizontal Run

(Vertical Round High Wind Termination

Shown)

High Altitude Installation

Your DESA direct-vent fireplace has been tested and approved for elevations from 0-2000 feet (USA) and elevations from 0-4500 feet (Canada).

When installing this fireplace at an elevation above 2000 feet (in the USA), you may need to decrease the input rating by changing the existing burner orifice to a smaller size. Reduce input 4% for each 1000 feet above sea level. Check with your local gas company for proper orifice size identification.

When installing this fireplace at an elevation above 4500 feet (in Canada), check with local authorities.

Consult your local gas company to help determine the proper orifice for your location.

For assistance with any high altitude installation contact DESA’s Customer Service Department at 1-866-672-6040.

116234-01E

www.desatech.com

17

Page 17
Image 17
Desa (V)TC36PE SERIES, (V)TC36NE SERIES installation manual High Altitude Installation, Vertical Venting