Desa VYM27PR installation manual Checking GAS Connections, Pressure Testing Heater Gas Connections

Models: VYM27PR

1 26
Download 26 pages 17.82 Kb
Page 12
Image 12

VANGUARD FLAME-MAX®

UNVENTED PROPANE/LP GAS LOG HEATER

INSTALLATION

Continued

A.G.A. Design-Certified

Manual Shutoff Valve

With 1/8" NPT Tap*

Approved Flexible Gas Hose (if allowed by local codes)

Gas Control

From External Regulator (11" W.C.** to 14" W.C. Pressure)

Pressure Testing Heater Gas Connections

1.

Open manual shutoff valve (see Fig-

 

ure 15).

2.

Open propane supply tank valve.

3.

Make sure control knob of heater is in

 

the OFF position.

4.

Check all joints from manual shutoff

 

valve to control valve (see Figure 16).

 

Apply mixture of liquid soap and wa-

 

ter to gas joints. Bubbles forming show

 

Tee

 

 

Joint

 

3" Minimum

Pipe

Sediment

 

Trap

 

Nipple

 

Cap

 

Figure 14 - Gas Connection

*Purchase the optional A.G.A. design-certified manual shutoff valve from your dealer. See Accessories, page 24.

**Minimum inlet pressure for purpose of input adjustment.

 

a leak.

5.

Correct all leaks at once.

6.

Light heater (see Operating Heater,

 

pages 14 through 16). Check all other

 

internal joints for leaks.

7.

Turn off heater (see To Turn Off Gas to

 

Appliance, page 15).

Manual

Shutoff Open

Valve

CHECKING GAS

CONNECTIONS

WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

CAUTION: Make sure exter- nal regulator has been installed between propane supply and heater. See guidelines under Con- necting to Gas Supply, page 11.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG

1.Disconnect heater and its individual manual shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator.

2.Cap off open end of gas pipe where manual shutoff valve was connected.

3.Pressurize supply piping system by ei- ther using compressed air or

opening propane supply tank valve.

4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

5.Correct all leaks at once.

6.Reconnect heater and manual shutoff valve to gas supply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG

1.Close manual shutoff valve (see Fig- ure 15).

2.Pressurize supply piping system by ei- ther using compressed air or opening propane supply tank valve.

3.Check all joints from propane supply tank to manual shutoff valve (see Fig- ure 15). Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

4.Correct all leaks at once.

Closed

Figure 15 - Manual Shutoff Valve

Propane

Manual Shutoff Valve

 

Supply Tank

 

Control Valve Location

Figure 16 - Checking Gas Joints

12

104675

Page 12
Image 12
Desa VYM27PR Checking GAS Connections, Pressure Testing Heater Gas Connections, Pressure Testing Gas Supply Piping System