
Operation
Continued
8.Keep control knob pressed in for 30 sec- onds after lighting pilot. After 30 seconds, release control knob.
•If control knob does not pop up when released, contact a qualified service
person or gas supplier for repairs. Note: If pilot goes out, repeat steps 4 thru
7. Wait one (1) minute before lighting pilot again.
9.Turn control knob counterclockwise
to desired heating level. The main burner should light. Manual control heat- ers should be used in locked positions.
10.To leave pilot lit and shut off burners only,
turn control knob clockwise
to the PILOT position.
WARNING: Always operate manual control heaters at the locked positions. Operation between these positions may create a possible health hazard if used in a poorly ventilated room. Read owner’s manual for complete instructions.
Ignitor Button | Control Knob |
CAUTION: Do not try to adjust heating levels by using the equipment shutoff valve.
TO TURN OFF GAS
TO APPLIANCE
1.Turn control knob clockwise
to the OFF position.
2.Turn off any electric power to the appli- ance if service is to be performed.
3.Close equipment shutoff valve (see Figure 14, page 12.
MANUAL LIGHTING
PROCEDURE
1.Remove front panel (see page 10).
2.Follow steps 1 through 7 under Lighting Instructions, page 13.
3.With control knob pressed in, strike match. Hold match to pilot until pilot lights.
4.Keep control knob pressed in for 30 sec- onds after lighting pilot. After 30 seconds, release control knob. Now follow step 9, under Lighting Instructions, column 2.
5.Replace front panel.
OFF
Figure 17 - Control Knob In The OFF Position (Manual Control Models)
Ignitor Button | Control Knob |
Figure 18 - Control Knob In The OFF
Position (Thermostat Models)
Thermocouple | Ignitor Electrode |
Pilot Burner
Figure 19 - Pilot (pilot may vary from
illustration)
THERMOSTAT
CONTROL OPERATION
Thermostat models only
The thermostatic control used on these models differs from standard thermostats. Standard thermostats simply turn on and off the burner. The thermostat used on this heater senses the room temperature. At times the room may exceed the set temperature. If so, the burner will shut off. The burner will cycle back on when room temperature drops below the set temper- ature. The control knob can be set to any heat level between 1 and 5. This adjusts the amount of gas flow to the burner. This increases or decreases the burner flame height.
Note: The thermostat sensing bulb measures the temperature of air near the heater cabinet. This may not always agree with room temperature (depending on housing construction, installation location, room size, open air temperatures, etc.). Frequent use of your heater will let you determine your own comfort levels.
14 | www.desatech.com |