DMP Electronics P83848 Light Distribution PER UL, Horizontal and Vertical Plane

Models: P83848

1 7
Download 7 pages 51.47 Kb
Page 3
Image 3

LIGHT DISTRIBUTION PER UL 1971:

Table 4: Horizontal and Vertical Plane

Angle

 

Horizontal

 

Vertical

(in deg.)

UL Min.

 

Typ. 15cd*

UL Min.

 

Typ. 15cd*

0

15.0

 

94

15.0

 

94

5

13.5

 

93

13.5

 

83

10

13.5

 

88

13.5

 

30

15

13.5

 

87

13.5

 

19

20

13.5

 

85

13.5

 

17

25

13.5

 

80

13.5

 

16

30

11.3

 

75

13.5

 

15

35

11.3

 

71

9.8

 

12

40

11.3

 

62

6.9

 

11

45

11.3

 

52

5.1

 

10

50

8.3

 

35

4.0

 

9

55

6.8

 

32

3.3

 

9

60

6.0

 

34

2.7

 

9

65

5.3

 

27

2.4

 

9

70

5.3

 

19

2.3

 

10

75

4.5

 

11

2.0

 

10

80

4.5

 

9

1.8

 

9

85

3.8

 

10

1.8

 

9

90

3.8

 

10

1.8

 

9

* 15cd models are UL Listed for 15cd and meet 75cd on axis.

WARNING: WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING PARTITIONS OR OTHER VIEWING OBSTRUCTIONS, SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT CAN BE SEEN BY ALL INTENDED VIEWERS, WITH THE INTENSITY, NUMBER, AND TYPE OF STROBES BEING SUFFICIENT TO MAKE SURE THAT THE INTENDED VIEWER IS ALERTED BY PROPER ILLUMINATION, REGARDLESS OF THE VIEWER'S ORIENTATION. FAILURE TO DO SO COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.

WARNING: THE AUDIBLE HORN STROBE APPLIANCES MUST BE FIELD SET TO THE DESIRED TONE AND dBA SOUND OUTPUT LEVEL BEFORE THEY ARE INSTALLED. THIS IS DONE BY PROPERLY INSERTING JUMPER PLUGS IN ACCORDANCE WITH THESE INSTRUCTIONS. INCORRECT SETTINGS WILL RESULT IN IMPROPER PERFORMANCE, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.

SOUND OUTPUT (SPL) SETTINGS:

NOTE: The Code 3 Horn incorporates the temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 off and repeat) specified by ANSI/NFPA for standard emergency evacuation signaling. The Code 3 Horn should be used

only for fire evacuation signaling and not for any other purpose.

Figure 1: Showing Location of Jumper Plug

Factory setting is on High dB and Code 3

P83848 A

Sheet 3 of 7

Page 3
Image 3
DMP Electronics P83848 Light Distribution PER UL, Horizontal and Vertical Plane, Sound Output SPL Settings