DOD PS-7 operation manual H - L mode Upper limit, Lower limit, Normal state No gas is detected

Models: PS-7

1 9
Download 9 pages 61.53 Kb
Page 8
Image 8
Normal state (No gas is detected)

H – H mode (1st level: Upper limit, 2nd level: Upper limit)

Full Scale

0ppm

2nd level gas alarm : ALARM 1 , ALARM 2 is displayed. Alarm contacts ZA1 and ZA2 are activated

Alarm value is set by entering A2 **

1st level gas alarm : ALARM 1 is displayed. Alarm contact ZA1 is activated

Alarm value is set by entering A1 **

Normal state (No gas is detected)

L – L mode (1st level: Lower limit, 2nd level: Lower limit)

25vol%

21vol%

0 vol%

Normal state

1st level alarm : ALARM 1 is displayed. Alarm contact ZA1 is activated.

Alarm value is set by entering A2 **

2nd level alarm : ALARM 1 , ALARM 2 is displayed. Alarm contact ZA1 and ZA2 are activated.

Alarm value is set by entering A1 **

H – L mode (Upper limit, Lower limit)

50vol%

21vol%

0 vol%

Upper alarm : ALARM 2 is displayed. Alarm contact ZA2 is activated. Alarm value is set by entering A2 **

Normal state

Lower alarm : ALARM 1 is displayed. Alarm contact ZA1 is activated. Alarm value is set by entering A1 **

* A2 value should be always greater than A1 value.

Page 8
Image 8
DOD PS-7 Normal state, H - L mode Upper limit, Lower limit, A2 value should be always greater than A1 value