Ramp Control

-2 accel/decel rates

-Frequency avoidance bands (3) to lock out mechanical resonance points.

-“S” curve acceleration and deceleration for smooth speed transitions

Time Stamped Fault Log

-User Interlock Open

-High DC Bus Voltage

-Low DC Bus Voltage

-Over-Current

-Over-Frequency

-Over-Temperature

-Electronic Motor Overload

-Ground Fault

-Others

Option Kits

-Braking resistors

-Remote NEMA 4 operator interface

-PC based V*S Utilities

-EMC line filters

-Network communications modules

-ControlNet

-DeviceNet

-Profibus

-Others

Stopping Modes

-DB Braking

-Ramp Stop

-Coast Stop

-DC Injection Braking

Operator Interface Modules

-Multi-line, 6-language graphical LCD OIM for local or remote operation. Allows drive control, configuration, monitoring and diagnostics. Function keys are configurable for desired functions.

Drive Protection

-Line-to-line and line-toground and output short circuit protection.

Instruction Manuals

D2-3485

(6SP Series - Frames A, B, C, D)

D2-3501

(6SB Series - Frames 2, 3, 4, 5, 6)

Service Conditions

• Elevation to 3300 ft.

(1000 meters); Derate 3% for every

1000 ft. above 3300 ft.

Operating temperature ranges:

-NEMA enclosures:

-0°C to 40°C (external ambient)

-IP20 enclosures:

-0°C to 50°C

(50 HP - 45°C; 200 HP - 40°C) (panel ambient)

Atmosphere non-condensing relative humidity: 5% to 95%

AC line voltage variation: rated input voltage ±10%

AC line frequency variation (50/60 Hz): 48 - 62 Hz

Storage temperature:

-- 40°C to 65°C (-40°F to 149°F)

Application Data

Pulse width modulation (PWM) sensorless vector control

Maximum load:

-110% continuous for one minute (Normal Duty Rating)

-150% continous for one minute (Heavy Duty Rating)

Frequency stability long term: 0.01% of base speed with digital keypad 0.5% of base speed with analog speed reference.

Linearity (speed reference to output frequency): ± 1.0%

Quiet Motor Operation Up to 200 Feet

The SP600 controller uses IGBT transistors switched at frequencies up to 10kHz to reduce PWM induced motor audible noise.

Unique transistor control circuits also allow drive to motor distances of up to 300 feet when applied with Reliance motors before output filtering considerations must be applied.

Tested to ensure that the waveform at the motor conduit box will not exceed the limits specified in NEMA MG1 31.40.4.2. at lead lengths of 200 ft.