INSTALLATION INSTRUCTIONS

FIG. 3

furnace thermostat leads must be routed to the roof opening of the air conditioner that will control it. Make sure that at least 15” of the furnace thermostat wires extend into the roof opening.

3/4” MIN.

LEAVE ACCESS FOR POWER SUPPLY WIRING

FRAME OPENING SO IT WON’T COL- LAPSE WHEN BOLTING DOWN AIR CONDITIONER

15”

min.

9.If an Energy Management System (load shed fea- ture) is to be used with the control, two wires must

be routed to the roof opening of the zone to be managed. The signal required for this function is normally open relay contact. When the EMS calls for the compressor to shut off, the relay contacts should close. Make sure at least 15” of the EMS wires extend into the roof opening.

10.Route a 4-conductor control cable from the Comfort Control Center™ mounting position into the 14-1/4” (±1/8”) roof opening. Make sure that at least 15” of the wire extends into the roof opening and 6” extend from the wall at the mounting position of the Comfort Control Center™.

11.In the event that other Air Conditioners are installed (additional zones) an additional 4-conductor control

cable must be routed to the other Air Conditioners. Make sure that at least 15” of the wire extends into the roof opening. (See Fig. 16)

12.If an automatic generator start kit (AGS) will be installed, a 4-conductor control cable must be routed from the last air conditioner to location of AGS kit. Follow AGS kit instructions for installation.

4.DOMETIC COMFORT CONTROL CENTER™ & CABLE INSTALLATION

It is the responsibility of the installer of this air condi- tioner system to ensure structural integrity of the RV roof. Never create a low spot on the roof where water will collect. Water standing around the air conditioner may leak into the interior causing damage to the product and the RV.

5.The 14-1/4” x 14-1/4” (±1/8”) opening is part of the return air system of the Air Conditioner and must be finished in accordance with NFPA Standard 501C

Section 2.7.

6.Route a dedicated 12 VDC supply line (18-22 AWG) from the RV’s converter or battery to the roof opening.

a.Wire must be fused at 3 Amps.

b.This supply line must be located in the front portion of the 14-1/4” (±1/8”) opening.

c.Make sure that at least 15” of supply wire extends into the roof opening.

d.In a multiple zone installation, this wiring is required in only one of the 14-1/4” (±1/8”) openings.

7.If a Remote Temperature Sensor is used, the connec- tor end must be routed to the roof opening of the

system which it will control. Make sure that at least 15” of the sensor cable extends into the roof opening. Refer to the Remote Sensor Instructions for details of

the installation.

8. If a furnace is to be controlled by the system, the two

A.LOCATION

1.If the system is to be used WITHOUT a Remote Temperature Sensor, the proper location of the Comfort Control Center™ is very important to ensure that it will provide a comfortable RV tempera- ture. Observe the following rules when selecting a location:

a. Locate the Comfort Control Center™ 54” above

the floor.

b.Install the Comfort Control Center™ on a partition, not on an outside wall.

c.NEVER expose it to direct heat from lamps, sun or other heat producing items.

d.Avoid locations close to doors that lead outside, windows or adjoining outside walls.

e.Avoid locations close to supply registers and the air from them.

2.If the system is to be used WITH a Remote Tem- perature Sensor in ALL zones, the Comfort Control Center may be mounted anywhere that is convenient

in the coach. Try to avoid hard to reach and hard to see areas.

a.Refer to the instructions provided with the Re- move Temperature Sensor for details of

installation.

Page 6
Image 6
Dometic 579 SERIES, 590 SERIES, 595 SERIES Dometic Comfort Control Center & Cable Installation, Location