CERTIFIED INSTALLATION

Certified installations require one roof vent and one lower side vent.

For “Certified Vent System Kits” see page 15.

For further information contact your dealer or distributor.

NOTE: The upper vent should be centered over the condenser coil at the back of the refrigerator.

Minimum ventilation height

Condenser

FIG. 9

METHODS OF INSTALLATION

The method of installation is shown in FIG. 9.

It is essential that all maximum or minimum dimensions are strictly maintained, as the performance of the refrig- erator is dependent on adequate flow of air over the rear of the refrigerator.

VENTILATION HEIGHTS

Installation with roof

Minimum ventilation

vent and lower side vent

heights in:

 

 

 

 

Refrigerator

Inches

mm

 

 

 

RM2652

57-3/4

1465

RM2852

63-3/4

1620

 

 

 

 

G

K

K

FIG. 10

L

 

NOTE: Wood Strip

MUST be in place

N

M

CLEARANCES

Minimum clearances in inches to combustible materials

are:

 

 

G:

Top

0

K:

Side

0

L:Bottom 0

M:Rear 0

N:See NOTE: Clearance “N” below.

NOTE: Clearance “M” is between the rearmost part of the refrigerator and the wall behind the refrigerator.

NOTE: Clearance “N” is the distance between the bot- tom of the lower side vent to the roof material. For ven- tilation height, see table VENTILATION HEIGHTS.

See Figures 9 and 10.

7