1.5. ANCHOR THE STOVE
The stove must be anchored to the floor with screws. Please use the two holes located on each side of the pedestal .
(See Fig. 9)
1.6. VENTING
In Canada, we recommend that you use a listed pellet vent that meets the ULC S-609-M89/ORD C 441-M90
Standard.
For the United States, we recommend that you use a listed pellet vent that meets the UL-641Standard.
This unit can be vented in an existing factory-built or masonry chimney with the addition of a liner, provided the
chimney is more than 4” in diameter. The liner should be listed and should meet the ULC S-635/640 standard in
Canada and the UL-1777 standard in the USA. Refer to the instructions provided by the vent or chimney
manufacturer, especially when passing through a wall, ceiling, or roof.
Your venting system should have at least one foot of vertical rise for each foot of horizontal run. Th e
total vertical rise should never be less than 3 feet (see Appendix A).
This unit uses a pressurized exhaust system. All vent connector joints m ust be sealed an d fastened. If vented
horizontally, joints should b e made gastight. Please consult the pellet pipe manufacturer‟s instruction to ens ure
proper installation and consistent performance to avoid smoke and ash spillage.
FIGURE 9
Anchor