ELATION Fireplace Insert 11
CLEARANCES
Clearance distances between the insert and any combustible material must be maintained while
installing your appliance:
Clearance to NON combustible hearth is: 0
Clearance to combustible mantel: 38” (965 mm)
Clearance to combustible side wall: 10” (254 mm)
Minimum hearth extension: 16” (406 mm)
INSTALLATION OF THE UNIT
Move the ELATION to the desired position. Mark the location for the gas inlet pipe and the
location where the vent is in relation to the fireplace flue. Remove the appliance.
Route a 3/8" minimum NPT iron pipe gas line to the desired location.
Install a shutoff valve to the gas line. Tighten securely using a pipe joint compound.
NOTE: The valve includes two ¼” tappings for test gauge connection. You may need,
however, to install a 1/8” plugged tapping between the gas line and the connection point to the
insert, if it is required by local codes.