Drolet ElDorado Reduced Clearances, Type Of Protection, Reducing Clearances With Shielding

Models: ElDorado Savannah Adirondack Jurassien Celtic

1 26
Download 26 pages 60.16 Kb
Page 12
Image 12
REDUCED CLEARANCES

REDUCED CLEARANCES

You may decrease the clearances by installing heat radiation shields between the walls or the ceiling and the stove. These heat radiation shields must be installed permanently, and can include sheet metal, a rigid non-combustible sheet or a masonry wall.

Clearances of not less than 1" (25 mm) and not more than 3" (76 mm) between the bottom of the shield and the floor and not less than 3" (76 mm) between the top of the shield and the ceiling must be respected to allow vertical air circulation behind the shield.

The shield must extend 20" (500 mm) above the stove top and 18" (450mm) to each side of the stove.

Following the installation of such a heat radiation shield, the clearances mentioned on the stove certification plate may be reduced as stated in the following table.

TYPE OF PROTECTION

Sheet metal, a minimum of 0,013" (0,33 mm) spaced out at least 7/8" (21 mm) by non-combustible spacers.

Ceramic tiles, or an equivalent non-combustible material on fire-proof supports spaced out at least 7/8" (21 mm) by non-combustible spacers.

Ceramic tiles, or an equivalent non-combustible material on fire-proof supports with a minimum of 0,013" (0,33 mm) sheet metal backing spaced out at least 7/8" (21 mm) by non-combustible spacers.

Brick spaced out at least 7/8" (21 mm) by non- combustible spacers.

Brick with a minimum of 0,013" (0,33 mm) sheet metal backing spaced out at least 7/8" (21 mm) by non- combustible spacers.

Reducing Clearances With

Shielding

Sides and

Top

Rear/Back

 

67%50%

50%33%

67%50%

50%N/A

67%N/A

Source: CSA Standard B365-1991, Table 4, Page 27

11

Page 12
Image 12
Drolet ElDorado, Savannah, Jurassien, Adirondack Reduced Clearances, Type Of Protection, Reducing Clearances With Shielding