Technical specifications

General

User interface

Graphical LCD with blue backlight and text in English,

 

French, German, Portuguese, Italian and Spanish

LEDs

Four status-indicating LEDs

Topology

Double-conversion

Diagnostics

Full system self-test

UPS bypass

Automatic bypass

Dimensions

See model selection guide

Rail kit

Included with all units

Electrical input

 

Nominal voltage

208V, 230V

 

200V, 208V, 220V, 230V, 240V and 250V

 

user-selectable

Voltage range

156–280 Vac (output PF 0.7)

Power draw of

5000 VA: 24.0A @208V

UPS (full load)

6000 VA: 28.8A @208V

Recommended

35A

input breaker

 

rating

 

Frequency

50/60 Hz autoselect

Frequency range

40–70 Hz

Electrical output

 

Power factor

0.7

On utility voltage

±2% of nominal

regulation

 

On battery

±2% of nominal

voltage regulation

 

Efficiency

>97% in high-efficiency mode; 91% in normal mode

Frequency

±3% Hz online

regulation

 

Load crest

3 to 1

factor

 

Battery

 

Internal battery

5.5 Ah, sealed, lead-acid; maintenance free

type

 

External battery

Up to four per 9135, rail kits included for

modules

rack mounting

EBM battery type

5.5 Ah, sealed, lead-acid; maintenance free

Battery runtime

Four (4) minutes with internal batteries @100%

 

load (0.7 PF)

 

For additional details, see battery runtime chart

Battery recharge

Six (6) hours to recover 90 percent of nominal backup

time

time after 100 percent RCD load discharge

Battery

Hot-swappable internal and external batteries

replacement

 

Start-on-battery

Allows start of UPS without utility input

Communications

Serial port

RS-232 as standard, RS-232 cable provided

USB port

As standard (HID)

 

 

 

Relay output

DB-9 Dry Contact—common alarm as standard

Communications

Optional communication slots (Mini X-Slot)

slot

 

 

 

 

 

 

Software

LanSafe UPS monitoring and management software

Environmental

 

 

 

 

 

 

Safety markings

208V: UL, NOM, NYCE

 

 

 

 

 

230V: CE, C-Tick, UL, GS

 

 

EMC markings

208/230V: FCC-A, VCCI-A, BSMI-A, C-Tick,

 

 

CE Compliance

 

 

 

Audible noise

Max 46 dB

 

 

 

Ambient

0˚C (32˚F) to +40˚C (104˚F)

 

 

operating

 

 

 

 

 

 

Storage

-20˚C (-4˚F) to +40˚C (104˚F) with batteries and

temperature

-25˚C (-13˚F) to +55˚C

 

 

 

 

 

(131˚F) without batteries

 

 

Relative humidity

5–90% non-condensing

 

 

 

Heat dissipation (BTUs/hour)

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating mode

Efficiency

 

5 kVA

6 kVA

 

 

 

 

 

 

 

 

 

 

Normal

 

91%

 

1150

1350

 

 

 

 

 

 

 

 

 

 

Battery

 

86%

 

1650

1960

 

 

 

 

 

 

 

 

 

High efficiency

97%

 

370

450

 

 

 

 

 

 

 

 

 

Back panel configurations

Choose from a variety of output receptacle combinations.

Hardwired models—230V

Hardwired models—208V

Power-corded models—208V

Back panel configurations vary by model type.

www.powerware.com 1.800.356.5794

5

Page 5
Image 5
Eaton Electrical 9135 warranty Safety markings, Operating mode Efficiency KVA, Back panel configurations