Powerware 9155/Powerware 9355 shown in perspective.

Premium power protection is now easier than ever.

With raised-floor real estate at a premium, you will appreciate that these UPSs are only 12” wide and 33” deep, including internal bat- teries. With such a small footprint, you have more location options, and more space is available for future expansion.

Equipment installation is easy, essentially plug-and-play. You can order either UPS with your choice of output receptacles with more than 17 types. To change or move data center equipment, you sim- ply unplug from the old receptacle, plug into a new one, and go. No need for an electrician to run new conduit and wiring.

Scalable architecture meets current and future load requirements.

Powerware 9155 UPSs are available in four models (8, 10, 12, and 15 kVA). Powerware 9355 UPSs come in 10 and 15 kVA models, so you can choose the configuration that most closely meets your capacity requirements and price point.

Powerware 9355 rear view with optional output receptacles

And you can scale from there. Using our signature Powerware Hot Sync paralleling technology, up to three (Powerware 9155) or up to four (Powerware 9355) equivalent UPS modules can be paralleled for extra capacity or redundancy. A 15 kVA UPS, for example, can grow to support loads of up to 45 kVA. There’s no dependence on communications wiring among those UPS modules.

Battery innovations optimize battery performance and service life.

Standard internal batteries provide power until auxiliary power takes over or systems are gracefully shut down. Battery runtime can be extended to hours by adding matching Extended Battery Modules (EBMs).

POWERWARE UPS BACKUP TIMES (IN MINUTES)

 

 

UPS

(1)

(2)

(3)

(4)

UPS

(1)

(2)

(3)

 

 

+ Internal

EBM

EBM

EBM

EBM

+ Internal

EBM

EBM

EBM

VA

Watt

32 Battery

64

64

64

64

64 Battery

96

96

96

15000

13500

4.6

23.0

43.0

65.1

88.6

13.3

43.0

76.7

113

14500

13050

4.9

24.1

45.2

68.3

93.0

14.1

45.2

80.5

119

14000

12600

5.2

25.2

47.3

71.5

97.4

14.9

47.3

84.2

125

13500

12150

5.5

26.4

49.4

74.7

102

15.8

49.4

88.1

130

13000

11700

5.8

27.6

51.6

78.1

106

16.7

51.6

92.0

136

12500

11250

6.1

28.8

54.0

81.6

111

17.6

54.0

96.2

142

12000

10800

6.5

30.2

56.5

85.5

116

18.6

56.5

101

149

11500

10350

6.9

31.6

59.3

89.7

122

19.2

59.3

106

156

11000

9900

7.3

33.3

62.4

94.4

129

20.2

62.4

111

164

10500

9450

7.8

35.1

65.9

99.6

136

21.4

65.9

117

174

10000

9000

8.4

37.2

69.8

106

144

22.6

69.8

124

184

9500

8550

9.1

39.6

74.2

112

153

24.1

74.2

132

196

9000

8100

9.9

42.3

79.4

120

163

25.7

79.4

141

209

8500

7650

10.8

45.5

85.2

129

175

27.6

85.2

152

225

8000

7200

11.9

49.1

91.9

139

189

29.8

91.9

164

242

7500

6750

13.1

53.2

99.7

151

205

32.3

99.7

178

263

7000

6300

14.6

58.0

109

164

224

35.2

109

194

286

6500

5850

16.3

63.5

119

180

245

38.6

119

212

314

6000

5400

18.4

70.0

131

198

270

42.5

131

234

346

5500

4950

20.1

77.6

145

220

300

47.2

145

259

383

5000

4500

22.4

86.6

162

245

334

52.6

162

289

428

4500

4050

25.2

97.4

182

276

376

59.2

182

325

-

4000

3600

28.6

110

207

313

426

67.1

207

369

-

3500

3150

32.8

127

238

359

-

77.0

238

423

-

3000

2700

38.3

148

277

418

-

89.7

277

-

-

2500

2250

45.6

176

329

-

-

107

329

-

-