Software and Accessories

Table 12. HMIEC0806/HMIEC1612 Function Specifications

Item

 

Specifications

Remark

 

 

 

 

 

 

Control Method

Stored program, cyclic

 

 

scan system

 

 

 

 

I/O Processing Method

Batch I/O (refresh)

Immediate refresh command available only

 

 

 

with I/O of the MPU

Execution Speed

Basic command (30 us)

Application command (30 ~ hundreds us)

 

 

 

Program Language

Commands + Ladder

Step commands included

 

 

Diagram + SFC

 

Program Capacity

999 Steps

Built-in EEPROM

 

 

 

 

Commands

 

Basic commands: 32

Application commands: 59

 

 

(including the STL

 

 

 

commands)

 

 

 

 

 

Step Relay

General Step

128 Points

S0 ~ S127

(Latched)

Point

 

 

Auxiliary

General

1024 Points

M0 ~ M511, M768 ~ M999, 744 points;

Relay

 

 

M1000 ~ M1279, 280 points

 

 

 

 

 

Latched

256 Points

M512 ~ M767

 

 

 

 

Timer

Digital

64 Points

T0 ~ T63 (100 ms time base)

 

 

 

 

 

 

63 Points

T64 ~ T126 (10 ms time base)

 

 

 

 

 

 

1 Points

T127 (1 ms time base)

 

 

 

 

Counter

General

112 Points

C0 ~ C111

 

 

 

 

 

Latched

16 Points

C112 ~ C127

 

 

 

 

 

32 bit

13 Points

C235,C236,C237,C238,C241,C242,

 

 

 

C244,C246,C247,C249,C251,C252, C254

 

 

 

(all of them are latched type)

 

 

 

 

Data

General

408 Points

D0 ~ D407

Register

 

 

 

Latched

192 Points

D408 ~ D599

 

 

 

 

 

Pointer

P

64 Points

P0 ~ P63

 

 

 

 

Index

E / F

2

E, F

Register

 

 

 

 

 

 

 

Constant

Decimal K

16 bit: -32768 ~ +32767

32 bit: -2147483648 ~ +2147483647

 

 

 

 

 

Hexadecimal H

16 bit: 0000 ~ FFFF

32 bit: 00000000 ~ FFFFFFFF

 

 

 

 

Self Diagnosis / Protection

I/O check, system execution timeout check, invalid command check,

 

 

program check and password settings

 

 

Monitor / Debug

Program execution time display, bit / word, device settings

 

 

 

 

M1000, M1001, M1002, M1003, M1020, M1021, M1022, M1067, M10068, and M1161 are the special auxiliary relays (special M).