Eaton Electrical Magnum Transfer Switch manual Transfer Switch Equipment Enclosures

Models: Magnum Transfer Switch

1 36
Download 36 pages 9.25 Kb
Page 15
Image 15

Instructional Booklet

Fixed and Drawout Magnum Transfer Switches

Effective: March 2007

Page 15

15. Auxiliary Contacts

Position indication contacts provide Form “A and “B” position con- tacts.

E.Source 1 Position: Provides one Form “A” and one Form “B” contact per customer connection.

F.Source 2 Position: Provides one Form “A” and one Form “B” contact for customer connection.

16. Integral Overcurrent Protection

Provides thermal-magnetic overcurrent protection integral to the power switching device(s). All Feature 16 options include a “Lockout” function. If the power switching device trips on an overcurrent condition, then “Lockout” is displayed on the ATS Controller display and automatic operation is prevented until the appropriate source is manually reset.

B.Both Power Source Switching Devices: Provides integral over- current protection on both Source 1 and Source 2 power switching devices.

E, Source 2 Power Switching Device: Provides integral overcur- rent protection on the Source 2 power switching device only.

N.Source 1 Power Switching Device: Provides integral overcur- rent protection on the Source 1 power switching device only.

18. Metering and Communications

The IQ Family of microprocessor-based multi-function monitoring and display devices features the latest technological advances in metering and communications capabilities. Feature 18 metering options include all required external devices (CT’s etc.) for a fully functioning metering system.

O. IQ Analyzer - Source 1 Line Side Metering: Provides an IQ Ana- lyzer for monitoring the Source 1 line side circuit.

P.IQ Analyzer - Source 2 Line Side Metering: Provides an IQ Ana- lyzer for monitoring the Source 2 line side circuit.

Q.IQ Analyzer with Selector Switch for Source 1 or Source 2 Line Side Metering: Provides an IQ Analyzer with a source selector switch for monitoring the Source 1 or Source 2 line side circuit.

R.IQ DP-4000 - Source 1 Line Side Metering: Provides an IQ DP- 4000 for monitoring the Source 1 line side circuit.

S.IQ DP-4000 - Source 2 Line Side Metering: Provides an IQ DP- 4000 for monitoring the Source 2 line side circuit.

T.IQ DP-4000 with Selector Switch for Source 1 or Source 2 Line Side Metering: Provides an IQ DP-4000 with a source selector switch for monitoring the Source 1 or Source 2 line side circuit.

20A. Rear Bus Connections

Provides Source 1, Source 2, and Load Circuit rear accessible bus stabs with provision for bus bar connection.

21A. Optional Power Cable Connection Terminals

Provides alternate power cable connection terminals. Consult Eaton for available optional terminal sizes.

37. Service Entrance Rated Transfer Switch

Provides the label “Suitable for use as Service Equipment” and the features necessary to meet the requirements for the label. Includes service disconnect with visible indication and neutral assembly with removable link. Feature 16 must be selected sepa- rately.

A.Service Equipment Rated Transfer Switch without Ground Fault Protection: Provides Service Equipment rating for an application that does not require ground fault protection.

B.Service Equipment Rated Transfer Switch with Ground Fault Protection: Provides Service Equipment rating for an applica- tion that requires ground fault protection.

41. Space Heater with Thermostat

Provides a space heater and adjustable thermostat. External con- trol power is not required.

C.Space Heater with Thermostat - 400 Watts: Provides a 400 Watt space heater with an adjustable thermostat.

42. Seismic Certification

Provides a Seismic Certified Transfer Switch with certificate for application that is Seismic Zone 4 under the California Building Code, the Uniform Building Code, and BOCA.

3.7 Enclosure

The rugged steel switch enclosure is supplied with four door hinges, regardless of enclosure size, to insure proper support of the door and door mounted devices. The hinges have removable hinge pins to facilitate door removal. The doors are supplied as standard with thumbscrew and padlock latches. Cable entry holes are the customer’s responsibility.

The door is used to mount a variety of lights, switches, and push buttons, depending upon the options required for a particular switch. All switch doors are supplied with a heavy duty plastic accessory panel in place, whether or not external devices are required. When lights, pushbuttons, or switches are required, they are normally mounted in the plastic door mounted panel.

Transfer switch enclosures and some internal steel mounting plates, such as the transformer panel mounting plate, go through

apre-treatment cleaning system prior to painting to insure a dura- ble finish. Should the enclosure become scratched and in need of touch up paint, use ANSI 61. All remaining steel is galvanized.

The standard switch enclosure is NEMA Type 1 for general indoor use (Table 4).

Table 4. Transfer Switch Equipment Enclosures.

NEMA TYPE

DESIGN

PROTECTION

1

Indoor

Enclosed Equipment

 

 

 

3R

Outdoor

Rain, Ice Formation

 

 

 

IB01602011E

For more information visit: www.Eaton.com

Page 15
Image 15
Eaton Electrical Magnum Transfer Switch manual Transfer Switch Equipment Enclosures

Magnum Transfer Switch specifications

The Eaton Electrical Magnum Transfer Switch is a premium solution designed for reliable power management in various applications, ranging from data centers to critical facilities. Known for its robust performance and advanced technology, the Magnum Transfer Switch ensures seamless transitions between utility and backup power sources, thereby enhancing operational continuity.

One of the standout features of the Eaton Magnum Transfer Switch is its unparalleled reliability. The switch is designed with heavy-duty components that provide up to 3,000 amps of continuous current with exceptional fault protection. Its construction is particularly suited for environments where power availability is crucial, ensuring that critical loads remain powered even during grid failures.

The Magnum Transfer Switch incorporates advanced technologies that simplify the operation and monitoring of power systems. It includes microprocessor-based controls that offer users customizable settings and configurations. These smart controls enable automatic transfer operations, ensuring quick response times when switching between power sources. The intelligent diagnostics feature further enhances reliability by offering predictive maintenance alerts, which help in identifying potential issues before they lead to failures.

Safety is a priority with the Magnum Transfer Switch. It is equipped with multiple interlocking features that prevent accidental switchovers and ensure that maintenance can be performed without the risk of electrical accidents. The design adheres to stringent safety standards, providing users with peace of mind.

Flexibility is another characteristic of the Eaton Magnum Transfer Switch. It offers a range of mounting options and configurations to fit diverse installation needs, whether in commercial infrastructures or industrial settings. The switch can be integrated with various power systems, making it a versatile choice for project developers and facility managers.

Additionally, the Magnum Transfer Switch supports eco-friendly initiatives through energy-efficient designs that minimize power loss during transfer operations. This feature is increasingly important as businesses aim to reduce their carbon footprint and enhance sustainability.

In summary, the Eaton Electrical Magnum Transfer Switch stands out for its reliable performance, advanced technologies, and robust safety measures. It is a versatile solution that meets the demands of modern power management, ensuring that critical systems operate continuously, even in the face of unexpected power interruptions. With its combination of efficiency, safety, and flexibility, the Magnum Transfer Switch remains a trusted choice for professionals in various industries.