MN05401014E 3
english

5. Technical data

Supply voltage:
DC power supply: 10 –30V DC/max. 40 mA
Display: 6 digits, red 7 segment
LED display, height 8 mm
[0.31 in.]
Data retention: EEPROM
Polarity of the inputs:
Programmable, npn or pnp
(sinking or sourcing) for all
inputs
Input resistance: appr. 5 kOhm
Count frequency:
Minimum pulse length for the reset input:
5 ms
Input sensitivity:
Standard sensitivity:
DC power supply: Low: 0 –0.2 x UB[V DC]
High: 0.6 x UB –30 [V DC]
UB= Supply Voltage
Pulse shape: any*,
Schmitt Trigger inputs
Ambient temperature:
-20 to +65°C [-4 to 149°F]
Storage temperature:
-25 to +70°C [-9 to 158°F]
EMC:
In compliance with the EC Directive
2004/108/EEC
Noise emission: EN 61 000-6-3/
EN 55 011 Class B
Noise immunity: EN 61 000-6-2
* at maximum frequency (50-50 duty cycle)
Housing: For front panel mounting
48 x 24 mm
[1.89 x 0.94 in.]
acc. to DIN 43700,
RAL 7021, dark grey
Weight: appr. 50 g [1.76 oz.]
Front panel rating: IP 65
Cleaning:
The front of the units is to be cleaned only with a
soft cloth moistened with water.

6. Terminal assignment

1 10 – 30V DC
2 0V GND
3 INP
4–
5 Reset
DC power supply: 24V 12V
Input level: Standard
typ. low level: 2.5V 2.0V
typ. high level: 22.0V 10V
Fmax:* 60 kHz 20 kHz
MN05401014E:MN05401014E 2/9/07 1:27 PM Page 3
CHS Controls AB