Ei Electronics manual Model Ei 164R Heat, Product Description, Operation, MAINS POWERED 230V~

Models: Ei 164R Heat

1 2
Download 2 pages 52.64 Kb
Page 1
Image 1
MAINS POWERED 230V~

MAINS POWERED 230V~

Rechargeable Battery Back-Up

Model Ei 164R Heat

Remote control capability

Easi-Fit base

Tamper proof rechargeable lithium battery back up

Fixed temperature fast response thermistor type sensor, range 54C to 62C

Test/Hush button

Advanced suppression and calibration technology

Interconnectable to other Ei mains powered alarms

Low power cell warning

Kitemarked to BS5446-2:2003

5 year guarantee

Product Description

The Ei164R is a Heat Alarm that runs on 230V AC mains power, and has built in tamper proof rechargeable lithium cells that act as a battery back up in the event of mains failure. These rechargeable lithium cells are designed to have a ten year life and outlast the life of the heat alarm itself, whilst providing up to six months of heat alarm operation without mains power.

The Ei164R is supplied with the Easi-Fit base that allows very quick and simple installation of the heat alarm, combined with simple detector head removal and replacement. The Easi-Fit base automatically connects both mains power and battery as the detector head slides on to the Easi-Fit base.

The Ei164R allows the detector to be controlled remotely by either a “Test/Hush” Switch (Ei152) or a Manual Call Point (MCP400). If the Ei164R is also interconnected to other Ei mains powered alarms then the whole system will be controllable remotely.

The Ei164R has built in circuitry to aid suppression of voltage transients and RF interference to further reduce the chances of false alarms under such conditions.

Heat alarms are ideal for use in kitchens and garages, where the use of optical or ionisation alarms would lead

Operation

The green indicator will illuminate to show mains power is present

The red indicator will flash every 40 seconds to show that the detector has performed an automatic self test

The red indicator will flash rapidly to show an alarm condition for the heat detector

The “Test/Hush” button will either silence false alarms or perform a unit self test

In “Test” mode the alarm will perform a self test and sound the horn

In “Hush” mode the alarm enters a ten minute period of reduced sensitivity to overcome false alarm conditions, and will then automatically reset itself

When interconnected to other Ei mains powered alarms, an alarm on one detector will trigger all other interconnected alarms within one second (only the triggered alarm will flash a red indicator)

The heat detector will emit a beep every 40 seconds to indicate that the battery back up is depleted and needs recharging

Shannon Free Zone, Shannon, Co. Clare, Ireland.

Ph.+353 61 471277 Fx.+353 61 471053

Email. eielectronics@eiltd.ie

www.eielectronics.com

Page 1
Image 1
Ei Electronics manual Model Ei 164R Heat, Product Description, Operation, MAINS POWERED 230V~