Marathon Monitors Inc.
AACC 2000 Carbon Nov. 1, 1997
75
Name Description Values Meaning
AAAA Alarm relay configuration
id Identity rELy Relay output
Func Function nonE No function
dIG Digital output
SEnS Digital output sense nor Normal (output energises when
TRUE, e.g. program events)
inv Inverted (output de-energises
when TRUE, e.g. alarms)
The following digital events appear after SEnS. Any one, or more, of the events can be
combined on to the output (see Fig. 6-2) by selecting YESin the lower readout.
1 - - -Alarm 1 active YES / no (- - -) = alarm type (e.g. FSL).
2 - - -Alarm 2 active YES / no If an alarm has not been
configured
3 - - -Alarm 3 active YES / no in AL ConFlist, then display
will
4 - - -Alarm 4 active YES / no differ:- e.g. Alarm 1 = ‘AL 1’.
mAn Controller in manual mode YES / no
Sbr Sensor break YES / no
SPAn PV out of range YES / no
Lbr Loop break YES / no
Ld.F Load failure alarm YES / no
tunE Tuning in progress YES / no
dc.F Voltage output open circuit, or mA
output open circuit YES / no
rmt.F module connection open circuit YES / no
iP1.F Input 1 Failure
IMP Impedance test in progress
burn Probe burn off in progress
VERi Probe verification in progress
VFLT Verification Fault
PFLT Probe Fault
nw.AL New Alarm has occurred YES / no
End End of setpoint rate limit, or end of
program YES / no
SYnc Program Synchronisation active YES / no