Marathon Monitors Inc.
Linear Input Scaling − The next 4 parameters only appear if a linear or sq rt input is chosen.
inp.L  | Displayed Value  | 
  | 
  | Input value low  | 
inp.H  | VAL. H  | 
  | 
  | Input value high  | 
  | 
  | 
  | ||
VAL.L | 
  | 
  | 
  | Displayed reading low  | 
VAL.H | VAL. L  | 
  | Electrical  | Displayed reading high  | 
  | 
  | |||
inP.L  | inP.H  | Input  | 
Name | Description  | Values  | Meaning  | 
  | 
  | 
  | 
  | 
SP  | Setpoint configuration | 
  | 
  | 
nSP  | Number of setpoints  | 2, 4, 16  | Select number of setpoints available  | 
rm.tr  | Remote Tracking  | OFF | Disable  | 
  | 
  | trAc  | Local setpoint tracks remote setpoint  | 
m.tr  | Manual Track  | OFF | Disable  | 
  | 
  | trAc  | Local setpoint tracks PV when in  | 
  | 
  | 
  | manual  | 
rmP.U  | Setpoint rate limit units  | PSEc  | Per second  | 
  | 
  | Pmin  | Per minute  | 
  | 
  | PHr  | Per hour  | 
rmt  | Remote setpoint configuration  | nonE  | Disable  | 
  | 
  | SP  | Remote setpoint  | 
  | 
  | Loc.t  | Remote setpoint + local trim  | 
  | 
  | rmt.t  | Remote trim + local setpoint  | 
AACC 2000 Carbon  | 72  | Nov. 1, 1997  |