Marathon Monitors Inc.
AACC 2000 Carbon Nov. 1, 1997
77
JAJA module config
NO configuration required
Name Description Values Meaning
1A1A/bb/CC(1) Module 1 configuration
id Identity of module installed nonE Module not fitted
rELy Relay output
dC.OP Non-isolated DC output
(1) If a dual-, or triple-, channel LoG Logic/ output
module is installed then the list LoG.i Logic input
headers 1b and 1C also appear SSr Triac output
dc.rE DC retransmission
(isolated)
dc.OP Isolated DC output
For ‘idid’ = ‘rELy’, ‘LoG’, or ‘SSr’ use this parameter table:
Func Function nonE Function disabled
dIG Digital output function
(Only Channels 1A and 1C can be HEAt Heating output
Heating, or Cooling) COOL Cooling output
up Open motorised valve
dwn Close motorised valve
(Only if id’ = ‘LoG’) SSr.1 mode 1 heating
(Only if id’ = ‘LoG’) SSr.2 mode 2 heating
VAL.L % PID demand signal
giving minimum output
Out.L
VAL.H % PID demand signal
giving maximum output
Out.H
Out.L Minimum average power
Out.H Maximum average power
SEnS Sense of output
(Only ifFunc’ = dIG’) nor Normal (output energises
when TRUE, e.g
program events)
inv Inverted (output de-
energises when TRUE,
e.g. alarms)
Notes:
1. When SEnS appears, then further parameters are available.
These are identical to those in the AA ConF list on Page 6-12.
VAL.L 100%0%
VAL.H
Displayed Value
Retransmitted
Output