Marathon Monitors Inc.
AACC 2000 Carbon Nov. 1, 1997
71
gsch Gain schedule enable no
yes Disabled
Enabled
pVpV Process value config
unit Inststrument units 0CCelsius
0FFarenheit
0kKelvin
dec.p Decimal places in the none Display units blanked
displayed value nnnn
nnn.n
nn.nn
None
One
Two
rng.l Range low Low range limit. Also setpoint limit for
alarms and programmers
rng.h Range high High range limit. Also setpoint limit for
alarms and programmers
Name Description Values Meaning
iPiP Input configuration
inPt Input type J.tc J thermocouple
k.tc K thermocouple
L.tc L thermocouple
r.tc R thermocouple (Pt/Pt13%Rh)
b.tc B thermocouple (Pt30%Rh/Pt6%Rh)
n.tc N thermocouple
t.tc T thermocouple
S.tc S thermocouple (Pt/Pt10%Rh)
PL 2PL 2 thermocouple
C.tc Custom downloaded t/c (default = type
C)
rtd 100 platinum resistance thermometer
mV Linear millivolt
voLt Linear voltage
mA Linear milliamps
Sr VSquare root volts
Sr ASquare root milliamps
* see “CUST” List. mV.C 8-point millivolt custom linearisation*
V.C 8-point Voltage custom linearisation*
mA.C 8-point milliamp custom linearisation*
Name Description Values Meaning
CJC Cold Junction Auto Automatic internal compensation
Compensation 0oC0oC external reference
45oC45oC external reference
50oC50oC external reference
OFF No cold junction compensation
imp Sensor Break Impedance Off Disabled (only with linear inputs)
Auto Factory set
Hi Impedance of input > 5K
Hi.Hi Impedance of input > 15K