configuration list. ‘func’ should be set to ‘Vpos’, ‘VAL.L’ must be set to ‘0’ and ‘VAL.H’ to ‘100’.

Exit from configuration and you are now ready to calibrate the position feedback potentiometer. Proceed as follows.

1.In Operator level, press the AUTO/MAN button to put the controller in Manual mode.

2.Drive the valve to its fully open position using .

3.Press until you get to ip-List’.

4.Press to get to PCAL-OFF’.

5.Press or to turn ‘PCAL’ to ‘on’.

6.Press and the upper readout indicates ‘Pot’.

7.Press or to get to Pot-3A.Hi’.(Assuming that the Potentiometer Input Module is in module position 3.)

8.Press to go to GO-no’.

9.Press or to see GO-YES’, which starts the calibration procedure.

10.Calibration is complete when the display returns to GO-no’.

11.Press and together to return directly to the Operator level.

12.The controller should still be in Manual mode.

13.Drive the valve to its fully closed position using .

14.Press until you get to ip-List’.

15.Press to get to PCAL-OFF’.

16.Press or to turn ‘PCAL’ to ‘on’.

17.Press and the upper readout indicates ‘Pot’.

18.Press or to get to Pot-3A.Lo

19.Press to go to GO-no’.

20.Press or to see GO-YES’, which starts the calibration procedure.

21.Calibration is complete when the display returns to GO-no’.

22.Press and together to return directly to the Operator level.

23.Press the AUTO/MAN button to place the controller in AUTO and the calibration of the position feedback potentiometer is now complete.