configuration list. ‘func’ should be set to ‘Vpos’, ‘VAL.L’ must be set to ‘0’ and ‘VAL.H’ to ‘100’.
Exit from configuration and you are now ready to calibrate the position feedback potentiometer. Proceed as follows.
1.In Operator level, press the AUTO/MAN button to put the controller in Manual mode.
2.Drive the valve to its fully open position using
.
3.Press
until you get to
4.Press
to get to
5.Press
or
to turn ‘PCAL’ to ‘on’.
6.Press
and the upper readout indicates ‘Pot’.
7.Press
or
to get to
8.Press
to go to
9.Press
or
to see
10.Calibration is complete when the display returns to
11.Press
and
together to return directly to the Operator level.
12.The controller should still be in Manual mode.
13.Drive the valve to its fully closed position using
.
14.Press
until you get to
15.Press
to get to
16.Press
or
to turn ‘PCAL’ to ‘on’.
17.Press
and the upper readout indicates ‘Pot’.
18.Press
or
to get to
19.Press
to go to
20.Press
or
to see
21.Calibration is complete when the display returns to
22.Press
and
together to return directly to the Operator level.
23.Press the AUTO/MAN button to place the controller in AUTO and the calibration of the position feedback potentiometer is now complete.