Marathon Monitors Inc.
AACC 2000 Carbon Nov. 1, 1997
70
CONFIGURATION PARAMETER TABLES
Name Description Values Meaning
inStinSt Instrument configuration
ZrFn Instrument Function Carb % Carbon
CtrL Control type Pid PID control
On.OF On/off control
VP Boundless motorised valve
control - no feedback
required
VP bBounded motorised valve
control - feedback required
tYPE Instrument USE ctrL
Mon Controller
Monitor
Act Control action rEv Reverse acting
dir Direct acting
CooL Type of cooling Lin Linear
oiL Oil (50mS minimum on-
time)
H2O Water (non-linear)
FAn Fan (0.5S minimum on-
time)
ProP Proportional only to error
on.OF On/off cooling
ti.td Integral & derivative SEc Seconds, OFF to 9999
time units min Minutes, OFF to 999.9
m-A Front panel Auto/Man button EnAb Enabled
diSA Disabled
r-h Front panel Run/Hold button EnAb Enabled
diSA Disabled
PwrF Power feedback on On
OFF Off
Fwd.t Feed forward type none None
FEEd Normal feed forward
SP.FF Setpoint feed forward
PV.FF PV feed forward
Sbr.t Sensor break output Sb.OP Go to pre-set value
HoLd Freeze output
FOP Forced manual output no Bumpless Auto/Manual
transfer
trac Returns to the Manual
value that was set when
last in Manual mode
Step Steps to forced output
level. Value set in ‘FOP’ of
op-List’ in Operator
Level
bcd BCD input function none
prog
sp
Not used
Select program number
Select setpoint number