Troubleshooting

8.0TROUBLESHOOTING

Table 14 Troubleshooting guide

Problem

Probable Cause

Remedy

 

 

 

Unit will not start

No power to unit

Check voltage to input circuit breaker.

 

 

 

 

Control voltage circuit

Locate short and reset breaker.

 

breaker open

 

 

Shut off by external

Check operation of thermostat.

 

thermostat or stat is

 

 

defective

 

No cooling

Low refrigerant

Check with gauges.

 

charge

 

 

Compressor contactor

Check voltage at contactor. If not present refer to print and determine

 

not pulling in

voltage loss. Check enthalpy sensor for full CCW or D setting.

 

No output from

Check operation of stat. Should have voltage output to Y terminal during

 

thermostat

cooling.

Unit cycles on

Loss or restriction of

Check condenser blower assembly for proper operation. Check for dirty

high pressure switch

air flow

coil or inlet grille restriction.

 

Defective fan cycling

Switch should make @ 240 PSIG ±10 (1655 kPa ±68.9). (Check settings

 

control

on adjustable switch when supplied.)

Heat does not operate

No voltage output

Check stat for proper output to W terminal.

 

from thermostat

 

 

Fuseable link blown

Check for open and replace.

 

 

 

 

Bad contactor

Check for open and replace.

 

 

 