Liebert® PSP™
Quick-Start Guide - 350VA/500VA, 120V
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and maintenance of the UPS.
•Intended for installation in a controlled environment.
•Maximum ambient temperature 104°F (40°C).
! CAUTION
To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit overcurrent protection in accordance with the national code, ANSI/NFPA 70.
•Do not connect equipment that may overload the UPS or demand
•Connect the UPS only to an earthed / grounded outlet that meets national and local electrical safety guidelines.
•Locate the UPS near a wall outlet. Do not use an extension cord between the UPS and the outlet.
•The Liebert PSP has been designed for small office/home office use only; it is NOT recommended for use in
•In the event of an emergency, press the On/Off button and disconnect the power cord from the AC power supply to properly disable the UPS.
•Do not attach power strips or surge suppressors to the UPS.
•Do not attempt to service any parts inside the UPS except when replacing the batteries. Failure to adhere to this could cause personal injury or equipment malfunction and void the warranty.
•For technical support:
•Visit www.liebert.com or
•Send an
SETUP
Step 1 Inspect the Package
Inspect the package and the UPS upon receipt.
Notify the carrier and dealer of visible damage.
The package includes:
• | Liebert PSP |
|
• | USB cable | USB |
• | cable |
The Liebert MultiLink™ software may be |
|
|
downloaded from the Liebert Web site at: | UPS | |
multilink.liebert.com | guide | |
|
|
See Step 8 for installation instructions.
Step 2 Decide Where to Place the UPS
The UPS must be placed indoors, protected from water, direct sunlight and excessive heat.
Provide at least 4" (100mm) of clearance on all sides of the unit for proper ventilation.
Step 3 Charge the UPS Battery Before Use
The UPS battery is not charged before shipping. It MUST be charged before use.
•Connect the UPS power cord to a wall outlet and charge for at least eight hours. Unit can be charged in the on or off state.
Note: If battery is placed in storage, charge the battery every six months if kept at 5°F to 85°F
Step 4 Start the UPS
After the battery is fully charged:
•Turn on the UPS by pressing the On/Off button (see Figure 1 below).
LED 1 should be illuminated (green), indicating the UPS is operating in Normal Mode.
Step 5 Check the Site Wiring Fault Indicator
• Check the rear of the UPS to make sure the Site Wiring Fault indicator is NOT illuminated.
Caution: If the Site Wiring Fault indicator is illuminated, have a qualified electrician check the wall receptacle wiring and fix any problems.
Step 6 Connect the Loads
The UPS has three battery backup outlets that provide power when the UPS operates on bat- tery. There is also one
• Plug the loads into the battery backup outlets on the rear of the UPS.
Caution: Do not connect a laser printer to the UPS.
Step 7 Connect the Network Surge Protection
The UPS has two network cable jacks for network lines (see Figure 2 below).
• Connect a
• Connect a network cable from the OUT jack on the rear of the UPS to a port on a PC or network device such as a router.
Step 8 Set Up Liebert MultiLink software
To start using the Liebert MultiLink software:
• Install the software.
See the Liebert MultiLink
• Connect one end of the USB cable (supplied) to the USB port on the rear of the UPS. Connect the other end to a USB port on the computer.
See the Liebert MultiLink user manual for operating instructions.
Note: Emerson recommends connecting the USB cable directly to the computer WITHOUT using a USB hub.
UPS CONTROLS AND CONNECTIONS
Figure 1 - Front Panel LEDs |
On/Off button |
Figure 2 - Rear Panel
LED 1 |
|
(green) |
|
Utility | ! |
symbol |
|
EM ERSON™ | Lieber t® PSP |
Network Power | AC Power System |
Overload symbol
LED 2 (red = fault; amber = overload)
Fault | |
symbol | Network |
| protection |
Surge outlet (1)
NEMA
Site Wiring
Fault indicator
USB interface
Resettable circuit protector
Battery backup |
outlets (3) |
NEMA |
UPS Status, Alarm Conditions and Alerts
Condition | LED | Color | Solid/Flashing | Audible Alarm |
|
|
|
|
|
Normal Mode | LED 1 | Green | Solid (steady glow) | (None) |
|
|
|
|
|
Battery Mode | LED 1 | Green | Flashes every 3 seconds | Every 3 seconds |
|
|
|
|
|
Battery Low | LED 1 | Green | Flashes every 1 second till end of discharge (EOD) | Every 1 second |
|
|
|
|
|
Overload | LED 2 | Amber | Solid (steady glow) until load drops or breaker trips | Continuous |
|
|
|
|
|
Battery Replacement | LED 2 | Red | Flashes every 1 second for 5 seconds only | Every 1 second for 5 seconds only |
|
|
|
|
|
Fault | LED 2 | Red | Solid (steady glow) until UPS shuts down after 5 seconds | Continuous until UPS shuts down |
|
|
|
|
|