Site Planning Data, Liebert FS Flywheel Energy Storage System: 190 kW, 10 Seconds
| Recharge |
| Discharge |
| Rotational Speed | Mechanical Data |
| ||||
Nominal Energy | Max. Current | Nom. Voltage | Nom. Power | Duration |
| Nom. Voltage | Min. | Max. | Dimensions | Weight | Losses |
Storage | ADC | VDC | kW | seconds |
| VDC | rpm | rpm | W x D x H, in. (mm) | lb. (kg) | (W) |
1900 | 50 | 520 | 190 | 10 |
| 510 | 25,000 | 55,500 | 25 x 32.5 x 71 | 1300 (590) | < 300 |
| (635 x 826 x 1803) | ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
See Notes for Table (below): | 1, 11 | 2, 11 | 4 | 4 |
| 3, 11 | — | — | — | — | — |
Notes for Table
1.Recharge current shown is the maximum the Liebert FS can accept. This value is dependent on the UPS, typically limited to 15% of the UPS’s nominal full load DC current.
2.Recharge voltage is adjustable, 480 to 500VDC. 190kW requires >520VDC.
3.Discharge voltage is adjustable, 480 to 500VDC. 190kW requires >510VDC.
4.Discharge rates below 190kW increase the discharge duration time (see Figure 1). In addition, the FS has the capability to discharge at rates above 190kW for shorter discharge durations. Please consult factory for details.
5.Power cable from UPS DC bus to Liebert FS should be sized for total maximum 2.0 volt line drop (power cable plus return cable drop as measured at the module) at maximum discharge current.
6.Grounding conductors to be sized per NEC
7.All wiring to be in accordance with National and Local Electrical Codes.
8.Minimum clearance is 3 ft. (0.9m) in front and 1 ft. (0.3m) above the Liebert FS.
9.Exterior cable entry available through removable top access plates: remove, punch to suit conduit size and replace.
10.Control wiring and power wiring must be run in separate conduit.
11.When used with the Liebert Series 300, nominal recharge voltage is 395VDC, nominal discharge voltage is 385VDC, with adjustable range of 360 to 405VDC for both. Due to lower VDC, power output below 30 seconds must be derated. Contact factory for details.
12.AC auxiliary power input required: 110/230VAC, 1 ph, 400VA.
Additional Notes
•If site configuration includes a backup emergency generator, it is recom- mended that the engine generator is set to be properly sized and equipped for a UPS application. Generator options would typically include an isosynchronous governor (generator frequency regulation) and a
Figure 1 DC bus power duration
1900
GT model, 510 VDC, with filter
10 seconds at 190kW (max. power)
@ 510 VDC min
© 2007 Liebert Corporation | ® Liebert and the Liebert logo are registered |
All rights reserved throughout the world. | trademarks of Liebert Corporation. All names referred |
Specifications subject to change without notice. | to are trademarks or registered trademarks of their |
| respective owners. |
Liebert Corporation
1050 Dearborn Drive | Telephone: |
P.O. Box 29186 | Facsimile: |
Columbus, OH 43229 | www.liebert.com |
|
|