5C06
WHITE-RODGERS
High Limit Control
Open On Rise, Manual Reset
INSTALLATION INSTRUCTIONS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
This high limit control is of the
This control is designed to break a line voltage (or low voltage) circuit if air temperature at its element location ever reaches its predetermined
This control may be used to protect against high tempera- tures in heating and ventilation systems by opening circuit to burner if circulated air reaches a temperature above the fixed setting of the control. It is also suitable for use on downflow furnaces to lock out burner in event of blower failure or slow start.
DESCRIPTION
PRECAUTIONS
!CAUTION
To prevent electrical shock and/or equipment damage, disconnect electric power to Furnace at main fuse or circuit breaker box, until installation is complete.
!WARNING
Do not use on circuits exceeding specified volt- ages. Higher voltages will damage control and could cause shock or fire hazard.
SPECIFICATIONS
ELECTRICAL DATA |
| THERMAL DATA |
|
|
|
| |
Electrical Rating: |
|
|
|
| |||
Motor Loads – 10 | FLA (60 | LRA), 120V 60 Hz. |
|
| |||
|
|
|
|
| |||
6 | FLA (36 | LRA), 240V 60 Hz. |
| ° | ° | ° | ° |
Valves & Relays– 4A @ 25V 60 Hz. | Standard | ||||||
° ° ° | ° |
|
|
| |||
|
|
| (52 , 74 , 93 , 116 C) |
|
|
| |
SWITCH ACTION: Open On Rise, Manual Reset | Element Insertion Length: 3 Inches |
|
|
|
Follow any wiring instructions provided by the furnace manufacturer. Typical diagram is shown for normal use of this control. A normal cycling type high limit control should always be used in addition to the High Limit Control for monitoring burner operation.
All wiring should be installed according to local and national electrical codes and ordinances. Controls are required to be installed with 75°C minimum wire.
LOCATION:
Normal use of this control requires that it be located in the return air duct where the sensing element will be subjected to normal flow of air returning to the furnace.
|
| WIRING | |
| FAN CONTROL | 5C06 HIGH LIMIT CONTROL | |
L1 | HOT |
| |
|
| ||
| POWER SUPPLY |
| |
L2 |
| TO OIL BURNER | |
|
| ||
BLOWER | OR GAS VALVE | ||
(LINE VOLTAGE) | |||
MOTOR | |||
|
ADJUSTMENT
This control has a fixed setting. If temperature ever reaches the
| |
EMERSON ELECTRIC CO. |
|
9797 REAVIS RD., ST. LOUIS, MO. 63123 |
|
(314) | Printed in U.S.A. |
9999 HWY. 48, MARKHAM, ONT. L3P 3J3 |
|
R (905) |
|
PART NO.
Replaces