Emerson 600 A, 400 TESTING & SERVICE continued, 1. Trouble-Shooting Checks, Manual Load Transfer

Models: 260 600 A 400

1 10
Download 10 pages 53.96 Kb
Page 9
Image 9
TESTING & SERVICE (continued)

TESTING & SERVICE (continued)

MANUAL LOAD TRANSFER

This procedure will manually transfer the load if the controller is disconnected.

Do not manually operate the transfer switch until both power sources are disconnected: open both circuit breakers.

1.Deenergize both the normal and emergency source conductors (remove fuses or open circuit breakers).

2.Use the maintenance handle to manually operate the transfer switch to the opposite source. See Manual Operation on page 1–3.

3.Then remove the maintenance handle. See page 1–3.

Verify that the maintenance handle has been removed before proceeding!

4.If the transfer switch is in the Emergency position manually start the engine generator and then install emergency source fuse or close the circuit breaker.

TROUBLE-SHOOTING

Note any optional accessories that may be furnished on the automatic transfer switch (ATS) and review their operation. Refer to any separate drawings and/or instructions that may be packed with the ATS.

Hazardous voltage capable of causing shock, burns, or death is used in this switch.

Do not touch the power or load terminals of the transfer switch!

Table 2-1. Trouble-Shooting Checks.

PROBLEM

CHECK IN NUMERICAL SEQUENCE

1

2

3

 

OPERATION

GEN-SET

VOLTAGE

Engine–generator set does

Hold Transfer Test switch 15

Starting control must be in the

 

not start when the Transfer

seconds or the outage must

automatic position. Batteries

 

Control switch is turned and

be long enough to allow for

must be charged and

 

held in Transfer Test position

Feature 1C time delay plus

connected. Check wiring to

or when the normal source

engine cranking and starting

engine starting contacts on

 

fails.

time.

customer terminal block TB.

 

 

 

Verify that the small plug J3 is

 

 

 

connected to receptacle P3.

 

 

 

 

 

Transfer switch does not

Wait for Feature 2B time delay

Generator output circuit

Voltmeter should read at least

transfer the load to the

to time out (if used).

breaker must be closed.

90% of nominal phase to

emergency source after the

 

Generator frequency must be

phase voltage between

engine–generator set starts.

 

at least 95% of nominal

transfer switch terminals EA

 

 

(57 Hz for a 60 Hz system.) *

and EC (or EL1 and EL2 for 2

 

 

 

pole switches). *

 

 

 

 

Transfer switch does not

Wait for Feature 3A time delay

 

Voltmeter should read at least

transfer the load to normal

to time out (if used).

 

90% of nominal phase to

source when normal returns

 

 

phase voltage between

or when the Transfer Control

 

transfer switch terminals NB

switch is released.

 

 

and NC, NC and NA, and NA

 

 

 

and NB (or NL1 and NL2 for 2

 

 

 

pole switches).

 

 

 

 

Engine–generator-set does

Wait for Feature 2E time delay

Starting control must be in the

 

not stop after load retransfer

to time out (if used).

automatic position.

to the normal source.

 

 

 

 

 

 

 

* These are factory settings. Refer to the Group 5 Controller User’s Guide.

If the problem is isolated to circuits on the controller or the transfer switch, call your local ASCO Power Technologies sales office or ASI. In the United States, call 1–800–800–2726. In Canada, call 1–800–234–2726. Furnish the Serial No. and Catalog No. from the transfer switch nameplate.

2---2

Page 9
Image 9
Emerson 600 A, 400, 260 manual TESTING & SERVICE continued, 1. Trouble-Shooting Checks, Manual Load Transfer, Problem