Specifications
| LIEBERT GXT2 6 KVA | LIEBERT GXT2 10 KVA |
Model Number | ||
Model Rating | 4200W/5200VA at 127/220 (120 or 240 degrees) | 8000W/8660VA at 127/220 (120 or 240 degrees) |
| 4200W/5200VA at 120/208 (120 or 240 degrees) | 8000W/8660VA at 120/208 (120 or 240 degrees) |
| 4200W/6000VA at 120/240 (180 degrees) | 8000W/10000VA at 120/240 (180 degrees) |
| 4200W/6000VA at 115/230 (180 degrees) | 8000W/10000VA at 115/230 (180 degrees) |
| 3780W/5400VA at 110/220 (180 degrees) | 7200W/9000VA at 110/220 (180 degrees) |
| 3360W/4800VA at 100/200 (180 degrees) | 6400W/8000VA at 100/200 (180 degrees) |
DIMENSIONS Unit W x D x H in. (mm) | 6.9 x 24.2 x 16.9 (176 x 615 x 430) | 10.5 x 26.0 x 16.9 (267 x 660 x 430) |
WEIGHT lbs (kg) Unit | 67 (30.3) | 109 (49.3) |
INPUT AC PARAMETERS
Nominal Operating Frequency |
| 50 or 60 Hz (Factory Default = 60) | |
Factory Default VAC |
| 120/208 VAC at 120 degrees | |
|
| 120 degrees | |
Allowable Input Phase Angle | 120, 180, 240 degrees, | ||
Factory Default |
| 120 VAC nominal | |
Input Frequency w/o Battery Operation |
| 40 - 70 Hz | |
OUTPUT AC PARAMETERS |
|
|
|
Factory Default VAC |
| 120/208 VAC @ 120 degrees | |
|
| 120 degrees | |
Allowable Output Phase Angle | 120, 180, 240 degrees | ||
Factory Default |
| 120 VAC nominal | |
User Configurable |
| 100/110/115/120/127 VAC, ±3% | |
Frequency |
| 50 Hz or 60 Hz, Nominal | |
Waveform |
| Sinewave | |
Overload Rating | 200% for 8 cycles; 130% for 10 seconds |
| 200% for 8 cycles then shutdown; 130% for 60 seconds |
| with transfer to bypass |
| with transfer to bypass |
ENVIRONMENTAL |
|
|
|
Operating Temp |
| +32°F to +104°F (0°C to +40°C) | |
Storage Temp |
| +5°F to +122°F | |
Relative Humidity |
| 0% to 95%, | |
Operating Elevation | Up to 10,000 ft. (3000m) at 104°F (40°C) without derating | ||
Storage Elevation |
| 50,000 ft. (15,000 m) maximum | |
Audible Noise | <55 dBA, at 1 meter from the rear; <50 dBA, at 1 meter from the front or sides | ||
AGENCY |
|
|
|
Safety | UL 1778, | ||
RFI/EMI |
| FCC Part 15, Subpart B, Class A | |
Surge Immunity |
| IEEE/ANSI C62.41 Category A & B | |
Transportation |
| ISTA Procedure 1A | |
|
|
|
|
INTERNAL BATTERY |
|
|
|
Model Number |
| ||
WEIGHT lbs (kg) | 79 (35.8) (one required) |
| 78.1 (35.5) (two required) |
Type | |||
Quantity x V x Rating | 12 x 12V x 9.0 AH (one required) |
| 12 x 12V x 9.0 AH (two required) |
Battery Mfg / Part # |
| Yuasa / REW | |
Recharge Time | 6 Hours to 90% capacity after full discharge into 100% load | ||
|
|
|
|
OPTIONAL EXTENDED BATTERY CABINET |
|
|
|
Model Number |
| ||
DIMENSIONS W x D x H in.(mm) | 3.5 x 24.2 x 16.9 (87 x 618 x 430) |
| 7.0 x 26.0 x 16.9 (178 x 660 x 430) |
WEIGHT lbs (kg) Unit | 93.6 (42.5) |
| 197.8 (89.9) (Total weight with batteries) |
BATTERY PARAMETERS |
|
|
|
Type | |||
Qty x V x Rating | 12 x 12V x 9.0 AH per kit |
| 12 x 12V x 9.0 AH per kit (two required) |
Battery Mfg / Part # |
| Yuasa / REW | |
ENVIRONMENTAL |
|
|
|
Operating Temp |
| +32°F to +104°F (0°C to +40°C) | |
Storage Temp |
| +5°F to +122°F | |
Relative Humidity |
| 0% to 95%, | |
Operating Elevation | Up to 10,000 ft. (3000m) at 104°F (40°C) without derating | ||
Storage Elevation |
| 50,000 ft. (15,000m) maximum | |
AGENCY |
|
|
|
Safety | UL 1778, | ||
RFI/EMI |
| FCC Part 15, Subpart B, Class A | |
Transportation |
| ISTA Procedure 1A |
Note: Part Numbers
14