Specifications

 

LIEBERT GXT2 6 KVA

LIEBERT GXT2 10 KVA

Model Number

GXT2-6000RT208

GXT2-10000RT208

Model Rating

4200W/5200VA at 127/220 (120 or 240 degrees)

8000W/8660VA at 127/220 (120 or 240 degrees)

 

4200W/5200VA at 120/208 (120 or 240 degrees)

8000W/8660VA at 120/208 (120 or 240 degrees)

 

4200W/6000VA at 120/240 (180 degrees)

8000W/10000VA at 120/240 (180 degrees)

 

4200W/6000VA at 115/230 (180 degrees)

8000W/10000VA at 115/230 (180 degrees)

 

3780W/5400VA at 110/220 (180 degrees)

7200W/9000VA at 110/220 (180 degrees)

 

3360W/4800VA at 100/200 (180 degrees)

6400W/8000VA at 100/200 (180 degrees)

DIMENSIONS Unit W x D x H in. (mm)

6.9 x 24.2 x 16.9 (176 x 615 x 430)

10.5 x 26.0 x 16.9 (267 x 660 x 430)

WEIGHT lbs (kg) Unit

67 (30.3)

109 (49.3)

INPUT AC PARAMETERS

Nominal Operating Frequency

 

50 or 60 Hz (Factory Default = 60)

Factory Default VAC

 

120/208 VAC at 120 degrees

L1-L2 Factory Default Input Phase Angle

 

120 degrees

Allowable Input Phase Angle

120, 180, 240 degrees, Auto-sensing on application of AC (Restrictions for L-N voltages other than 120 VAC)

Factory Default L1-N, L2-N VAC

 

120 VAC nominal

Input Frequency w/o Battery Operation

 

40 - 70 Hz

OUTPUT AC PARAMETERS

 

 

 

Factory Default VAC

 

120/208 VAC @ 120 degrees

L1-L2 Factory Default Output Phase Angle

 

120 degrees

Allowable Output Phase Angle

120, 180, 240 degrees Auto-sensing on initial application of input AC

Factory Default L1-N, L2-N VAC

 

120 VAC nominal

User Configurable L1-N, L2-N VAC

 

100/110/115/120/127 VAC, ±3%

Frequency

 

50 Hz or 60 Hz, Nominal

Waveform

 

Sinewave

Overload Rating

200% for 8 cycles; 130% for 10 seconds

 

200% for 8 cycles then shutdown; 130% for 60 seconds

 

with transfer to bypass

 

with transfer to bypass

ENVIRONMENTAL

 

 

 

Operating Temp

 

+32°F to +104°F (0°C to +40°C)

Storage Temp

 

+5°F to +122°F (-15°C to +50°C)

Relative Humidity

 

0% to 95%, non-condensing

Operating Elevation

Up to 10,000 ft. (3000m) at 104°F (40°C) without derating

Storage Elevation

 

50,000 ft. (15,000 m) maximum

Audible Noise

<55 dBA, at 1 meter from the rear; <50 dBA, at 1 meter from the front or sides

AGENCY

 

 

 

Safety

UL 1778, c-UL Listed (Suitable for computer room applications)

RFI/EMI

 

FCC Part 15, Subpart B, Class A

Surge Immunity

 

IEEE/ANSI C62.41 Category A & B

Transportation

 

ISTA Procedure 1A

 

 

 

 

INTERNAL BATTERY

 

 

 

Model Number

GXT2-144BATKIT (one required)

 

GXT2-288RTBKIT (two required)

WEIGHT lbs (kg)

79 (35.8) (one required)

 

78.1 (35.5) (two required)

Type

Valve-regulated, non-spillable, flame retardant, lead acid

Quantity x V x Rating

12 x 12V x 9.0 AH (one required)

 

12 x 12V x 9.0 AH (two required)

Battery Mfg / Part #

 

Yuasa / REW 45-12 FR

Recharge Time

6 Hours to 90% capacity after full discharge into 100% load

 

 

 

 

OPTIONAL EXTENDED BATTERY CABINET

 

 

 

Model Number

GXT2-144VBATT

 

GXT2-288RTVBATT (requires two GXT2-288RTBKIT)

DIMENSIONS W x D x H in.(mm)

3.5 x 24.2 x 16.9 (87 x 618 x 430)

 

7.0 x 26.0 x 16.9 (178 x 660 x 430)

WEIGHT lbs (kg) Unit

93.6 (42.5)

 

197.8 (89.9) (Total weight with batteries)

BATTERY PARAMETERS

 

 

 

Type

Valve-regulated, non-spillable, flame retardant, lead acid

Qty x V x Rating

12 x 12V x 9.0 AH per kit

 

12 x 12V x 9.0 AH per kit (two required)

Battery Mfg / Part #

 

Yuasa / REW 45-12 FR

ENVIRONMENTAL

 

 

 

Operating Temp

 

+32°F to +104°F (0°C to +40°C)

Storage Temp

 

+5°F to +122°F (-15°C to +50°C)

Relative Humidity

 

0% to 95%, non-condensing

Operating Elevation

Up to 10,000 ft. (3000m) at 104°F (40°C) without derating

Storage Elevation

 

50,000 ft. (15,000m) maximum

AGENCY

 

 

 

Safety

UL 1778, c-UL Listed (Suitable for computer room applications)

RFI/EMI

 

FCC Part 15, Subpart B, Class A

Transportation

 

ISTA Procedure 1A

Note: Part Numbers GXT2-6000RT208 and GXT2-10000RT208 do not include internal battery kits. When calculating total unit weight, add weight of internal batteries.

14

Page 14
Image 14
Emerson 6 kVA, 10 kVA manual Specifications

10 kVA, 6 kVA specifications

Emerson, a leader in power management solutions, offers a range of uninterruptible power supply (UPS) systems that ensure critical systems remain operational during power disturbances. Among their notable offerings are the Emerson 6 kVA and 10 kVA models, designed for reliability, efficiency, and innovation.

The Emerson 6 kVA and 10 kVA UPS systems are engineered to provide high-quality power protection. They deliver a rugged design suitable for various applications, including data centers, telecommunications, and industrial environments. These models boast a compact footprint, enabling them to fit within limited spaces while accommodating significant power needs.

One of the central features of these UPS systems is their advanced double-conversion technology. This method converts incoming AC power to DC and then back to AC, ensuring a continuous and clean power supply, free from surges, sags, or electrical noise. This technology is essential for sensitive electronic equipment that requires reliable power to function optimally.

Additionally, both the 6 kVA and 10 kVA models are equipped with a high-efficiency mode, which allows them to operate with lower energy consumption during periods of stable power. This feature not only reduces operational costs but also minimizes the environmental impact, making the systems more sustainable.

Emerson’s UPS systems also integrate adaptive battery management technology. This system extends battery life by intelligently monitoring and controlling the charging and discharging processes. Users can enjoy longer-lasting performance, minimizing the frequency and cost associated with battery replacements.

Moreover, the user-friendly interface of these UPS systems provides real-time monitoring and diagnostic capabilities. LED indicators and an intuitive display equip operators with crucial information about the system's status, ensuring they can respond quickly to any arising issues.

Scalability is another hallmark of Emerson’s 6 kVA and 10 kVA UPS models. They can be easily integrated into existing systems, enabling businesses to expand their operations without the need for complete overhauls of their power infrastructure.

In conclusion, Emerson's 6 kVA and 10 kVA UPS systems are designed for organizations that prioritize operational continuity and power quality. With their advanced technologies, robust features, and commitment to efficiency, these models stand out as reliable solutions for safeguarding critical electronic equipment against power disruptions.