Application Engineering |
|
|
|
|
B U L L E | T | I | N |
Table 2 Continued
1.Run capacitor has failed
2.Low line voltage (contact utility if voltage at disconnect is low)
Yellow “ALERT” | Locked Rotor | • Check wiring connections | |
Flash Code 4 | 3. Excessive liquid refrigerant in compressor | ||
|
4.Compressor bearings are seized
•Measure compressor oil level
1.Evaporator blower is not running
•Check blower relay coil and contacts
•Check blower motor capacitor
•Check blower motor for failure or blockage
•Check evaporator blower wiring and connectors
Yellow “ALERT” | Compressor (Moderate Run) | • | Check indoor blower control board |
Flash Code 5 | Trip | • | Check thermostat wiring for open circuit |
2.Faulty metering device
•Check TXV bulb installation (size, location and contact)
•Check if TXV/fixed orifice is stuck closed or defective
3.Condenser coil poor air circulation (dirty, blocked, damaged)
4.Low refrigerant charge
Yellow “ALERT” | Welded Contactor | 1. | Compressor contactor has failed closed |
Flash Code 8 | Compressor always runs | 2. | Thermostat demand signal not connected to module |
Yellow “ALERT” | Low Supply Voltage | 1. | Control Circuit transformer is overloaded |
Flash Code 9 | Voltage below 18V | 2. | Low line voltage (contact utility if voltage at disconnect is low) |
“LOCKOUT” Flash Codes
1.Condenser fan is not running
•Check fan capacitor
•Check fan wiring and connectors
Red “LOCKOUT” | Compressor (Pressure) Trip | • Check fan motor for failure or blockage | |
Compressor is locked out | 2. High head pressure | ||
Flash Code 2 | |||
after 4 consecutive or 10 total | • Check high pressure switch if present in system | ||
Yellow Off | |||
compressor (pressure) trip events | • Check if system is overcharged with refrigerant | ||
|
•Check for
3.Condenser coil poor air circulation (dirty, blocked, damaged)
4.Return air duct has substantial leakage
Red “LOCKOUT” | Pressure Switch Cycling | 1. Time delay relay or control board defective | ||
Compressor is locked out after 4 | ||||
Flash Code 3 | ||||
consecutive or 10 total pressure | 2. | If high pressure switch present go to Flash Code 2 information | ||
Yellow Off | ||||
cycling events |
|
| ||
|
|
| ||
|
| 1. | Run capacitor has failed | |
Red “LOCKOUT” | Locked Rotor | 2. | Low line voltage (contact utility if voltage at disconnect is low | |
| • Check wiring connections | |||
Flash Code 4 | Compressor is locked out after 10 |
| ||
3. | Excessive liquid refrigerant in compressor | |||
Yellow Off | consecutive locked rotor events | 4. | Compressor bearings are seized | |
|
| |||
|
|
| • Measure compressor oil level |