Emerson AE8-1385 Application Engineering, B U L L E, Continued, Compressor Moderate Run, Trip

Models: AE8-1385

1 12
Download 12 pages 54.27 Kb
Page 12
Image 12
Open Start Circuit

Application Engineering

 

 

 

 

B U L L E

T

I

N

AE8-1385

Table 2 Continued

 

 

1.

Evaporator blower is not running

 

 

 

Check blower relay coil and contacts

 

 

 

Check blower motor capacitor

 

Compressor (Moderate Run)

 

Check blower motor for failure or blockage

Red “LOCKOUT”

Trip

 

Check evaporator blower wiring and connectors

Compressor is locked out

 

Check indoor blower control board

Flash Code 5

 

after 4 consecutive or 10 total

 

Check thermostat wiring for open circuit

Yellow Off

 

compressor (moderate run) trip

2.

Faulty metering device

 

 

events

 

Check TXV bulb installation (size, location and contact)

 

 

 

• Check if TXV/fixed orifice is stuck closed or defective

 

 

3.

Condenser coil poor air circulation (dirty, blocked, damaged)

 

 

4.

Low refrigerant charge

 

 

1.

Run capacitor has failed

Red “LOCKOUT”

 

2.

Open circuit in compressor start wiring or connections

Open Start Circuit

 

Check wiring and connectors between supply and the

Flash Code 6

 

Current only in run circuit

 

 

compressor “S” terminal

Yellow Off

 

 

 

3.

Compressor start winding is damaged

 

 

 

 

 

Check compressor motor winding resistance

 

 

1.

Open circuit in compressor run wiring or connections

Red “LOCKOUT”

 

 

Check wiring and connectors between supply and the

Open Run Circuit

 

 

compressor “R” terminal. Confirm proper wire routing per

Flash Code 7

 

 

Current only in start circuit

 

 

Figure 1.

Yellow Off

 

 

 

2.

Compressor run winding is damaged

 

 

 

 

 

Check compressor motor winding resistance

Red “LOCKOUT”

Over Current Protection

1.

Check for contactor shorted to ground

Current to PROT is greater than

Flash Code 10

2.

Check for mis-wiring to the PROT terminal

2A mps

 

 

 

 

The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Emerson Climate Technologies, Inc. reserves the right to modify the designs or specifications of such products at any time without notice. Emerson Climate Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson Climate Technologies, Inc. product remains solely with the purchaser and end-user.