Application Engineering |
|
|
|
|
B U L L E | T | I | N |
Table 2 Continued
|
| 1. | Evaporator blower is not running | ||
|
|
| • | Check blower relay coil and contacts | |
|
|
| • | Check blower motor capacitor | |
| Compressor (Moderate Run) |
| • | Check blower motor for failure or blockage | |
Red “LOCKOUT” | Trip |
| • | Check evaporator blower wiring and connectors | |
Compressor is locked out |
| • | Check indoor blower control board | ||
Flash Code 5 |
| ||||
after 4 consecutive or 10 total |
| • | Check thermostat wiring for open circuit | ||
Yellow Off |
| ||||
compressor (moderate run) trip | 2. | Faulty metering device | |||
| |||||
| events |
| • | Check TXV bulb installation (size, location and contact) | |
|
|
| • Check if TXV/fixed orifice is stuck closed or defective | ||
|
| 3. | Condenser coil poor air circulation (dirty, blocked, damaged) | ||
|
| 4. | Low refrigerant charge | ||
|
| 1. | Run capacitor has failed | ||
Red “LOCKOUT” |
| 2. | Open circuit in compressor start wiring or connections | ||
Open Start Circuit |
| • | Check wiring and connectors between supply and the | ||
Flash Code 6 |
| ||||
Current only in run circuit |
|
| compressor “S” terminal | ||
Yellow Off |
|
| |||
| 3. | Compressor start winding is damaged | |||
|
| ||||
|
|
| • | Check compressor motor winding resistance | |
|
| 1. | Open circuit in compressor run wiring or connections | ||
Red “LOCKOUT” |
|
| • | Check wiring and connectors between supply and the | |
Open Run Circuit |
|
| compressor “R” terminal. Confirm proper wire routing per | ||
Flash Code 7 |
|
| |||
Current only in start circuit |
|
| Figure 1. | ||
Yellow Off |
|
| |||
| 2. | Compressor run winding is damaged | |||
|
| ||||
|
|
| • | Check compressor motor winding resistance | |
Red “LOCKOUT” | Over Current Protection | 1. | Check for contactor shorted to ground | ||
Current to PROT is greater than | |||||
Flash Code 10 | 2. | Check for | |||
2A mps | |||||
|
|
|
|
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Emerson Climate Technologies, Inc. reserves the right to modify the designs or specifications of such products at any time without notice. Emerson Climate Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson Climate Technologies, Inc. product remains solely with the purchaser and